{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1096-4ED32-0JC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1096-4ED32-0JC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1096-4ED32-0JC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1096-4ED32-0JC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1096-4ED32-0JC0, 3-pole molded case circuit breaker, 16 A rated current, TM210 thermal-magnetic release, 121 kA interrupting at 240 V.","salesMarkdown":"The interrupting ratings tell you where it can clear a fault without welding or rupturing: 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V. That 121 kA at 240 V is the headline number — it means this breaker can safely interrupt a fault current up to 121,000 A on a 240 V line, which covers most secondary-side transformer faults in industrial distribution. The 16 A rating holds across 45 °C to 55 °C; above that it derates to 15 A at 60 °C through 70 °C, so if the panel runs hot you lose 1 A of headroom. The 3VA1096-4ED32-0JC0 measures 76.2 mm wide, 130 mm tall, and 70 mm deep — a standard 3-pole MCCB footprint that drops into a SENTRON panelboard or a DIN-rail adapter. It's a straight line-protection breaker: feed it, protect the downstream cable or bus, and move on.","metaTitle":"Siemens SENTRON 3VA1096-4ED32-0JC0 MCCB, 16 A, 121 kA at 240","metaDescription":"Siemens SENTRON 3VA1096-4ED32-0JC0 molded case circuit breaker, 3-pole, 16 A, TM210 release, 121 kA at 240 V. Current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"121 kA","at 415 V":"75.6 kA","at 440 V":"52.5 kA","at 500 V":"11.9 kA","at 690 V":"11.9 kA","at 45 °C":"16 A","at 50 °C":"16 A","at 55 °C":"16 A","at 60 °C":"15 A","at 65 °C":"15 A","at 70 °C":"15 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Product version":"Line protection","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10.6 W","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA10964ED320AA0","Courant permanent assigné Iu":"16 A","Ground-Fault Monitoring Version":"Without","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","reference code / acc. to IEC 81346-2":"Q","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL32","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product Extension / Optional / Motor Drive":"No","Adjustable response value current / lg min.":"1","Adjustable response value current / li max.":"320 A","Adjustable response value current / li min.":"320 A","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"S","Max. rated operational current of the frame size":"100 A","Mechanical Service Life (Switching Cycles) / Typical":"20 000","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5 mm","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=82595&mlfb=3VA1096-4ED32-0JC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1096-4ED32-0JC0/alternatives.json"},"ai":{"faq":[{"question":"What is the interrupting rating of 3VA1096-4ED32-0JC0 at 240 V?","answer":"121 kA at 240 V, which is the highest interrupting rating on this breaker — it clears faults up to 121,000 A at that voltage."},{"question":"Where can I buy 3VA1096-4ED32-0JC0?","answer":"We source this part to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the depth of 3VA1096-4ED32-0JC0?","answer":"70 mm (2.76 in)."},{"question":"What is the width of 3VA1096-4ED32-0JC0?","answer":"76.2 mm (3 in)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1096-4ED32-0JC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1096-4ED32-0JC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}