{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1096-4ED42-0AA0-ZD00","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1096-4ED42-0AA0-ZD00","canonicalUrl":"https://aoctrl.com/siemens/3VA1096-4ED42-0AA0-ZD00","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1096-4ED42-0AA0-ZD00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1 IEC frame 100, breaking capacity class S, Icu=36kA @ 415V, 4-pole, line protection TM210, FTFM, In=16A, overload protection Ir=16A fixed, short-circuit protection Ii=20 x In, N conductor unprotected, nut keeper kit for DC Power OEM in China.","salesMarkdown":"The Siemens 3VA1096-4ED42-0AA0-ZD00 is a 4-pole IEC frame 100 molded case circuit breaker from the 3VA1 series, rated for line protection with a TM210 thermal-magnetic trip unit. The fixed overload protection is set at Ir = 16 A, and the short-circuit pickup is fixed at Ii = 20 × In (320 A), so there is no adjustment range on either; what you order is what protects the circuit. The neutral conductor is unprotected on this variant, and the unit includes a nut keeper kit specified for DC Power OEM builds in China. For a panel with a calculated fault current of, say, 25 kA at the bus, this breaker has margin. The Ii = 20 × In (320 A) magnetic pickup means it will trip instantaneously on a short-circuit above that level; for motor-starting inrush or transformer energization, verify that the peak transient does not exceed 320 A, or you risk nuisance trips. The fixed Ir = 16 A overload setting suits a continuous load drawing up to 16 A — no dial to turn, so the load current must be known and stable.","metaTitle":"Siemens 3VA1096-4ED42-0AA0-ZD00 Circuit Breaker, 36kA @ 415V","metaDescription":"Siemens 3VA1096-4ED42-0AA0-ZD00 IEC frame 100 circuit breaker, breaking capacity class S, Icu=36kA @ 415V, 4-pole, In=16A, TM210, FTFM. Lifecycle stage current. Sourced to order ag","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1667506&mlfb=3VA1096-4ED42-0AA0-ZD00","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1096-4ED42-0AA0-ZD00/alternatives.json"},"ai":{"faq":[{"question":"What is the listed description of 3VA1096-4ED42-0AA0-ZD00?","answer":"The description is: circuit breaker 3VA1 IEC frame 100 breaking capacity class S Icu=36kA @ 415V 4-pole, line protection TM210, FTFM, In=16A overload protection Ir=16A fixed short-circuit protection Ii=20 x In N conductor unprotected nut keeper kit for DC Power OEM in China."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1096-4ED42-0AA0-ZD00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1096-4ED42-0AA0-ZD00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}