{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1102-5MG32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1102-5MG32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1102-5MG32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1102-5MG32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1102-5MG32-0AA0, molded case circuit breaker, starter protection design, 3-pole, 2 A rated, 187 kA interrupting at 240 V AC, TM110M overcurrent release, IP40 front.","salesMarkdown":"## What this breaker is for The Siemens 3VA1102-5MG32-0AA0 is a SENTRON molded case circuit breaker (MCCB) explicitly designed for starter protection — meaning it's meant to sit ahead of a motor contactor and overload relay, not as a feeder breaker for general distribution. The 2 A continuous rating (flat across 40 °C to 70 °C, no derate needed) and the TM110M thermal-magnetic release are sized for small motor loads or control transformers where the branch circuit needs coordinated short-circuit protection without nuisance tripping on inrush. ## Interrupting capacity — the real number The headline figure is 187 kA at 240 V — that's the short-circuit current this breaker can safely clear at the lowest common industrial voltage. At 415 V it still holds 121 kA, dropping to 75.6 kA at 440 V and settling at 7.5 kA for both 500 V and 690 V. For a 2 A frame, those are high-endurance numbers; the breaker isn't the weak link in a high-fault panel. The 800 V rated insulation voltage confirms it's built for 690 V systems without creepage concerns. ## Physical fit and panel integration Three-pole, 70 mm deep, 76.2 mm wide, 130 mm tall. That's a compact MCCB footprint — fits standard DIN-rail or screw-mount panel layouts. IP40 on the front means it's protected against tools and wires >1 mm but not sealed against dust ingress; keep it inside a rated enclosure for washdown areas. No trip indicator, no undervoltage release, no ground-fault monitoring — this is a bare-bones starter protector, not a multifunction breaker.","metaTitle":"Siemens 3VA1102-5MG32-0AA0 SENTRON MCCB, 2A, 187kA at 240V","metaDescription":"Siemens 3VA1102-5MG32-0AA0 SENTRON molded case circuit breaker, starter protection design, 2A rated, 187kA interrupting at 240V. 3-pole, TM110M release. Active production. Availabl","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"70 mm","Poles":"3","Width":"76.2 mm","Height":"130 mm","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e80d24a82ac943a22b8ccf5ed6d92854.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=802438&mlfb=3VA1102-5MG32-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1102-5MG32-0AA0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1102-5MG32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1102-5MG32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}