{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1102-6MG32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1102-6MG32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1102-6MG32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1102-6MG32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1, molded case circuit breaker (MCCB), 3-pole, 2 A, TM110M thermal-magnetic release, 220 kA at 240 V, IP40 front, 70 mm deep.","salesMarkdown":"## MCCB for starter protection It is designated for starter protection — meaning it is sized to sit ahead of a motor contactor and protect the branch circuit against short circuits, not to provide overload protection for the motor itself (that is the overload relay's job). The interrupting capacity is 220 kA at 240 V, 154 kA at 415 V, and 121 kA at 440 V, which drops to 7.5 kA at 500 V and 690 V. That high short-circuit rating at low voltage tells you this breaker is designed for high-fault locations — typically a main or subfeed in a panel with a large transformer upstream. The 2 A rating is fixed — not adjustable. The TM110M release has a fixed magnetic trip at 32 A (li min and li max both 32 A), so it will hold through motor inrush up to that level before instantaneously tripping. Power loss is 1.5 W maximum, negligible for panel thermal budgeting. The breaker is 3-pole and does not support a neutral pole upgrade. Dimensions: 130 mm high, 76.2 mm wide (3 inches), 70 mm deep. The breaker accepts an optional motor drive (remote operator) for automated disconnection.","metaTitle":"Siemens 3VA1102-6MG32-0AA0 SENTRON MCCB, 2 A, 220 kA at 240","metaDescription":"Siemens 3VA1102-6MG32-0AA0 SENTRON molded case circuit breaker, 2 A rated, 3-pole, TM110M release, 220 kA at 240 V. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","title":"3VA1102-6MG32-0AA0","Height":"130 mm","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"121 kA","at 500 V":"7.5 kA","at 690 V":"7.5 kA","at 45 °C":"2 A","at 50 °C":"2 A","at 55 °C":"2 A","at 60 °C":"2 A","at 65 °C":"2 A","at 70 °C":"2 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","description":"circuit breaker 3VA1 IEC frame 160 breaking capacity class H Icu=70kA @ 415V 3-pole, starter protection TM110M, FM, In=2A without overload protection short-circuit protection Ii=15 x In nut keeper kit","Number Of Poles":"3","Product version":"Starter protection","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Communication Function":"No","Phase Failure Detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"1.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Courant permanent assigné Iu":"2 A","Ground-Fault Monitoring Version":"Without","Tension assignée d'isolement Ui":"800 V","Design Of The Overcurrent Release":"TM110M","protection class IP / on the front":"IP40","reference code / acc. to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Adjustable response value current / li max.":"32 A","Adjustable response value current / li min.":"32 A","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"I","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Max. rated operational current of the frame size":"160 A","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5 mm","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/88c3fe4a89a31ae7e027cdf9d46e7a7e.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=802440&mlfb=3VA1102-6MG32-0AA0"},"ai":{"faq":[{"question":"Where can I buy 3VA1102-6MG32-0AA0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the interrupting capacity of this MCCB at 240 V?","answer":"220 kA at 240 V, dropping to 154 kA at 415 V, 121 kA at 440 V, and 7.5 kA at both 500 V and 690 V."},{"question":"What is the rated current of 3VA1102-6MG32-0AA0?","answer":"2 A continuous, fixed — not adjustable. The magnetic trip is fixed at 32 A."},{"question":"Does 3VA1102-6MG32-0AA0 include ground-fault monitoring or communication?","answer":"No. This is a plain thermal-magnetic MCCB with no ground-fault monitoring, no phase failure detection, and no communication function."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1102-6MG32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1102-6MG32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}