{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1104-6MG36-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1104-6MG36-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1104-6MG36-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1104-6MG36-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1104-6MG36-0AA0, molded case circuit breaker (MCCB), starter protection, 3-pole, 4 A, TM110M release, 220 kA at 240 V.","salesMarkdown":"## What the 220 kA breaking capacity means for your panel What sets it apart is the interrupting capacity: 220 kA at 240 V, 154 kA at 415 V, and 121 kA at 440 V. The 3VA1104-6MG36-0AA0 measures 70 mm deep by 76.2 mm wide by 130 mm high — a standard MCCB footprint that fits most DIN-rail or panel-mount enclosures. The optional motor drive (Product Extension / Optional / Motor Drive: Yes) allows remote closing or opening via a separate accessory — useful for automated restart schemes. ## Release and protection characteristics The TM110M overcurrent release is a fixed thermal-magnetic type: the thermal element protects against overloads (4 A continuous), and the magnetic element trips instantaneously on short-circuit at a fixed threshold of 64 A (li min. and li max. both 64 A). That means the magnetic pickup is not adjustable — if your motor inrush exceeds 64 A, this breaker will nuisance-trip on start.","metaTitle":"Siemens 3VA1104-6MG36-0AA0 SENTRON MCCB, 4A, 220kA at 240V","metaDescription":"Siemens SENTRON 3VA1104-6MG36-0AA0 molded case circuit breaker, 4 A, 3-pole, TM110M release, 220 kA at 240 V. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","title":"3VA1104-6MG36-0AA0","Height":"130 mm","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"121 kA","at 500 V":"7.5 kA","at 690 V":"7.5 kA","at 45 °C":"4 A","at 50 °C":"4 A","at 55 °C":"4 A","at 60 °C":"4 A","at 65 °C":"4 A","at 70 °C":"4 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","description":"circuit breaker 3VA1 IEC frame 160 breaking capacity class H Icu=70kA @ 415V 3-pole, starter protection TM110M, FM, In=4A without overload protection short-circuit protection Ii=15 x In clamp connection","Number Of Poles":"3","Product version":"Starter protection","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Communication Function":"No","Phase Failure Detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"5.4 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Courant permanent assigné Iu":"4 A","Ground-Fault Monitoring Version":"Without","Tension assignée d'isolement Ui":"800 V","Design Of The Overcurrent Release":"TM110M","protection class IP / on the front":"IP40","reference code / acc. to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Adjustable response value current / li max.":"64 A","Adjustable response value current / li min.":"64 A","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"I","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Max. rated operational current of the frame size":"160 A","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1.5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d18744b0b2f057e7c199d0fc7e8db0b5.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=802437&mlfb=3VA1104-6MG36-0AA0"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA1104-6MG36-0AA0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm number."},{"question":"What is the breaking capacity of 3VA1104-6MG36-0AA0 at different voltages?","answer":"220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and 7.5 kA at both 500 V and 690 V."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1104-6MG36-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1104-6MG36-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}