{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1110-1AA36-0AG0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1110-1AA36-0AG0","canonicalUrl":"https://aoctrl.com/siemens/3VA1110-1AA36-0AG0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1110-1AA36-0AG0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1110-1AA36-0AG0, switch disconnector in MCCB design, 3-pole, 100 A rated current flat to 70 °C, 690 V AC / 500 V DC, IP40 front, front terminal connection.","salesMarkdown":"The Siemens 3VA1110-1AA36-0AG0 is a SENTRON switch disconnector in MCCB design — 3-pole, rated 100 A continuous, with no overload or short-circuit protection built in. It is a straight disconnect, not a breaker; the trip curve is absent because there is no trip unit. That is unusual for a molded-case switch and simplifies the BOM calculation. Power loss is 38 W maximum, which is the heat the enclosure must shed. Mechanical service life is 15 000 operating cycles typical. The auxiliary switch configuration is one auxiliary switch plus one trip alarm switch, both HP type, with two CO contacts total. Dimensions are 130 mm height, 76.2 mm width, 70 mm depth — a 3-pole MCCB footprint. Front terminal connection with clamp terminals for the main circuit. Motor drive is available as an optional extension.","metaTitle":"Siemens 3VA1110-1AA36-0AG0 SENTRON Switch Disconnector, 100","metaDescription":"Siemens 3VA1110-1AA36-0AG0 SENTRON switch disconnector, 100 A rated current flat to 70 °C, 3-pole, IP40 front, active production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Switch disconnector","Undervoltage Release":"No","Design Of The Product":"in MCCB design","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"38 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Design Of The Auxiliary Switch":"1 auxiliary switch + 1 trip alarm switch HP","Design Of The Auxiliary Release":"Without auxiliary release","Insulation Voltage / Rated Value":"800 V","protection class IP / on the front":"IP40","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","Product Function / Communication Function":"No","Undervoltage Release With Leading Contact":"No","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","number of CO contacts / for auxiliary contacts":"2","Mechanical Service Life (Operating Cycles) / Typical":"15 000","Type Of Electrical Connection / For Main Current Circuit":"Terminal connection","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=120384&mlfb=3VA1110-1AA36-0AG0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1110-1AA36-0AG0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA1110-1AA36-0AG0?","answer":"Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels."},{"question":"What is the closest functional second-source to 3VA1110-1AA36-0AG0?","answer":"The 5SQ2370-2YA05 is a different class of device — a 0.5 A miniature circuit breaker, not a 100 A switch disconnector. It will not drop into the same panel position or carry the same load. No direct second-source exists for this MCCB-form switch disconnector."},{"question":"Will 3VA1110-1AA36-0AG0 drop into a panel specified around 5SQ2370-2YA05?","answer":"No. The 5SQ2370-2YA05 is a 55 mm deep MCB; this switch disconnector is 70 mm deep, 76.2 mm wide, and rated 100 A. The footprint, terminal arrangement, and current rating are incompatible."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1110-1AA36-0AG0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1110-1AA36-0AG0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}