{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1110-3ED22-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1110-3ED22-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1110-3ED22-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1110-3ED22-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1110-3ED22-0AA0, molded case circuit breaker, 2-pole, 100 A at 40 °C, 75.6 kA at 240 V, TM210 thermal-magnetic release, line protection.","salesMarkdown":"The Siemens 3VA1110-3ED22-0AA0 is a 2-pole SENTRON molded case circuit breaker rated for 100 A continuous at 40 °C, with no derating needed up to 50 °C — it still carries a full 100 A at 50 °C. Above that, the thermal curve steps down: 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. That means in a warm panel you lose less than 10 % of capacity even at the upper operating limit. The interrupting rating is 75.6 kA at 240 V AC and 52.5 kA at 415 V AC, which covers most industrial panelboard and distribution board fault levels. It's a line-protection device, not a motor-circuit protector, so it's sized for feeder or branch-circuit duty where you need a simple, reliable thermal-magnetic trip curve. The 2-pole format suits single-phase or two-phase loads, or a 2-pole branch on a 3-phase system. The breaker measures 70 mm deep, 50.8 mm wide (2 inches), and 130 mm high. That 2-inch width per pole is the standard SENTRON 3VA footprint — it clips onto the mounting plate or DIN rail without needing extra adaptors for most panel layouts. The 50.8 mm width also matches the typical 2-module spacing on a DIN-rail terminal block row, so fill-factor planning is straightforward. That keeps the wiring simple: line in, load out, no control-power connections needed. The trip indicator is absent, so you'd rely on the handle position or a downstream status contact for remote indication.","metaTitle":"Siemens 3VA1110-3ED22-0AA0 SENTRON MCCB, 100A, 2-Pole, 75.6k","metaDescription":"Siemens 3VA1110-3ED22-0AA0 SENTRON molded case circuit breaker, 100A at 40°C, 2-pole, 75.6kA at 240V, TM210 release. Current lifecycle, available to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"50.8 mm","Height":"130 mm","at 240 V":"75.6 kA","at 415 V":"52.5 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"98 A","at 60 °C":"96 A","at 65 °C":"94 A","at 70 °C":"91 A","Depth [In]":"2.76 in","Width [In]":"2 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"2","Product version":"Line protection","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"16.66 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"500 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","operating voltage / at AC / rated value":"415 V","Max. rated operational voltage Ue with DC":"250 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"N","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6,5 mm","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f353dbcf269eaeb39fa4a9819817964a.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=130936&mlfb=3VA1110-3ED22-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1110-3ED22-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Does 3VA1110-3ED22-0AA0 have a communication function or trip indicator?","answer":"No — this variant has no communication function, no trip indicator, no undervoltage release, and no motor drive. It is a basic thermal-magnetic breaker with LI protection only."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1110-3ED22-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1110-3ED22-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}