{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1110-3EE36-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1110-3EE36-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1110-3EE36-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1110-3EE36-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1110-3EE36-0AA0, molded case circuit breaker, 3-pole, 100 A at 40 °C, breaking capacity 75.6 kA at 240 V, TM220 release, line protection.","salesMarkdown":"Breaking capacity reaches 75.6 kA at 240 V AC, 52.5 kA at 415 V, and 32 kA at 440 V, so it handles high-fault utility feeds or large transformer secondaries without cascading upstream. The breaker measures 130 mm high, 76.2 mm wide, and 70 mm deep, fitting standard SENTRON 3VA mounting footprints. Above that, the continuous current drops linearly: 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. Maximum power loss is 25 W at rated load — a figure to budget for in enclosed panel thermal calculations.","metaTitle":"Siemens 3VA1110-3EE36-0AA0 SENTRON MCCB, 100A, 3-Pole, 75.6k","metaDescription":"Siemens SENTRON 3VA1110-3EE36-0AA0 molded case circuit breaker, 100A rated at 40°C, 3-pole, breaking capacity 75.6kA at 240V. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"75.6 kA","at 415 V":"52.5 kA","at 440 V":"32 kA","at 500 V":"11.9 kA","at 690 V":"11.9 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"98 A","at 60 °C":"96 A","at 65 °C":"94 A","at 70 °C":"91 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"25 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM220","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"N","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b86ab82001ca483f4c5ac5dd3dc9a0d4.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=85621&mlfb=3VA1110-3EE36-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1110-3EE36-0AA0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA1110-3EE36-0AA0?","answer":"Submit an RFQ through this listing. The part is sourced to order; pricing and stock are confirmed at quote time."},{"question":"When sourcing 3VA1110-3EE36-0AA0, what's the closest functional second-source?","answer":"The closest functional peer within the SENTRON family is the 3VA1010-2ED32-0JA0, but it is a lower-current variant with a different release and breaking capacity. Verify your load and fault-current requirements before substituting — the 3VA1110-3EE36-0AA0 carries 100 A and higher interrupting ratings at 240 V and 415 V."},{"question":"What is 3VA1110-3EE36-0AA0's listed depth?","answer":"The depth is 70 mm (2.76 in)."},{"question":"What is 3VA1110-3EE36-0AA0's listed width?","answer":"The width is 76.2 mm (3 in)."},{"question":"Will 3VA1110-3EE36-0AA0 drop into a panel specified around 3VA1010-2ED32-0JA0 without rewiring?","answer":"The mounting footprint and pole configuration are the same (3-pole, same SENTRON 3VA frame), so it will physically fit and the bus connections align. However, the 3VA1110-3EE36-0AA0 is rated for 100 A versus the lower rating of the 3VA1010-2ED32-0JA0 — verify that the downstream conductors and upstream protection are sized for the higher continuous current before swapping."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1110-3EE36-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1110-3EE36-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}