{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1110-4GF46-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1110-4GF46-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1110-4GF46-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1110-4GF46-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1110-4GF46-0AA0, molded case circuit breaker, 4-pole, 100 A rated continuous current, 121 kA breaking capacity at 240 V, line protection version.","salesMarkdown":"The Siemens 3VA1110-4GF46-0AA0 is a 4-pole SENTRON molded case circuit breaker rated for 100 A continuous current (Iu) across the 40 °C to 50 °C band — no derating needed in that range. At 55 °C it still carries 98 A, at 60 °C 96 A, and at 65 °C 94 A, so the thermal curve is shallow enough that a warm panel enclosure won't force an upsized frame. The 121 kA breaking capacity at 240 V (76 kA at 415 V, 53 kA at 440 V, 11.9 kA at 500 V and 690 V) means this breaker can interrupt very high fault currents at lower voltages — typical for a main or feeder breaker in a 240 V or 400 V distribution board where the utility transformer is close. The TM240 overcurrent release is a thermal-magnetic design, so no external trip unit to configure; it's set at the factory for the 100 A rating. The breaker measures 70 mm deep, 101.6 mm wide, and 130 mm high — a standard 4-pole MCCB footprint that fits most DIN-rail or panel-mount enclosures without surprises.","metaTitle":"Siemens 3VA1110-4GF46-0AA0 SENTRON MCCB, 100 A, 4-Pole, 121","metaDescription":"Siemens SENTRON 3VA1110-4GF46-0AA0 molded case circuit breaker, 100 A rated, 4-pole, 121 kA breaking at 240 V. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"101.6 mm","Height":"130 mm","at 240 V":"121 kA","at 415 V":"76 kA","at 440 V":"53 kA","at 500 V":"11.9 kA","at 690 V":"11.9 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"98 A","at 60 °C":"96 A","at 65 °C":"94 A","at 70 °C":"91 A","Depth [in]":"2.8 in","Width [in]":"4 in","Height [in]":"5.1 in","Number of poles":"4","Product version":"Line protection","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"25 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-40 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Ground fault monitoring version":"Without","Design of the overcurrent release":"TM240","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Design of the N-conductor protection":"100%","Reference code / acc. to DIN EN 81346-2":"Q","Max. rated operational voltage Ue with DC":"600 V","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 000 A","Adjustable response value current / li min.":"500 A","Adjustable response value current / lr min.":"70 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LI","Switching capacity class of the circuit breaker":"S","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1.5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a14ccee4ec2c7370cdc2ea7c90e69a7f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=18572&mlfb=3VA1110-4GF46-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1110-4GF46-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What is 3VA1110-4GF46-0AA0's listed depth?","answer":"The depth is 70 mm (2.8 in), with a width of 101.6 mm (4 in) and height of 130 mm (5.1 in)."},{"question":"Will 3VA1110-4GF46-0AA0 drop into a panel specified around 3VA1010-2ED32-0JA0 without rewiring?","answer":"No — the 3VA1110-4GF46-0AA0 uses a thermal-magnetic TM240 release, while the 3VA1010-2ED32-0JA0 uses an electronic trip unit. The trip unit difference requires a different control wiring scheme and protection coordination study, so they are not drop-in replacements."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1110-4GF46-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1110-4GF46-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}