{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1110-5ED32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1110-5ED32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1110-5ED32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1110-5ED32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1110-5ED32-0AA0, molded case circuit breaker, 3-pole, 100 A, TM210 trip, 187 kA at 240 V.","salesMarkdown":"Interrupting capacity is 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 500/690 V. That covers most low-voltage distribution fault levels in North American and IEC installations; the 690 V figure matters for 600 V class Canadian or mining panels. The 76.2 mm width (3 inches) is standard for a 3-pole MCCB on DIN rail or panel-mount — fits a 3-module footprint. IP40 on the front face; suitable for dry indoor enclosures where no washdown is required. If you need remote tripping or GF protection, you add external accessories or step to a 3VA1 variant with those options. The closest sibling is 3VA1110-5ED36-0AC0 — same frame, same 100 A rating, same TM210 trip, but with a different interrupting capacity curve and possibly a higher short-time rating. The deciding factor is the fault level at your secondary bus: if your available fault current exceeds the 3VA1110-5ED32-0AA0's rating at your voltage, the -5ED36 variant may be the correct choice.","metaTitle":"Siemens 3VA1110-5ED32-0AA0 SENTRON MCCB, 100A, 3-Pole, 187kA","metaDescription":"Siemens SENTRON 3VA1110-5ED32-0AA0 molded case circuit breaker, 100A, 3-pole, 187kA interrupting at 240V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","title":"3VA1110-5ED32-0AA0","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"75.6 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"98 A","at 60 °C":"96 A","at 65 °C":"94 A","at 70 °C":"91 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","description":"circuit breaker 3VA1 IEC frame 160 breaking capacity class M Icu=55kA @ 415V 3-pole, line protection TM210, FTFM, In=100A overload protection Ir=100A fixed short-circuit protection Ii=10 x In nut keeper kit","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"25 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/39ffa6aaf0f3a46c5a2457c126316b70.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=357399&mlfb=3VA1110-5ED32-0AA0"},"ai":{"faq":[{"question":"Where can I buy 3VA1110-5ED32-0AA0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability."},{"question":"What is the interrupting capacity of 3VA1110-5ED32-0AA0 at 415 V?","answer":"121 kA at 415 V. The full curve: 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, 17 kA at 500 V and 690 V."},{"question":"What is the depth of 3VA1110-5ED32-0AA0?","answer":"70 mm (2.76 inches). Overall dimensions: 130 mm high, 76.2 mm wide, 70 mm deep."},{"question":"Will 3VA1110-5ED32-0AA0 drop into a panel specified around 3VA1110-5ED36-0AC0?","answer":"Yes, the two breakers share the same physical footprint (130 × 76.2 × 70 mm) and mounting pattern, so no rewiring or panel modification is needed."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1110-5ED32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1110-5ED32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}