{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1110-5ED32-0BH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1110-5ED32-0BH0","canonicalUrl":"https://aoctrl.com/siemens/3VA1110-5ED32-0BH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1110-5ED32-0BH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1110-5ED32-0BH0, molded case circuit breaker, 3-pole, 100 A, TM210 thermal-magnetic release, line protection, 70 mm depth.","salesMarkdown":"The interrupting ratings climb with voltage: 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 690 V. That spread tells you the breaker is built for high-fault installations — the 121 kA at 415 V covers most European industrial distribution, while the 75.6 kA at 440 V handles North American 480 V panels with headroom. What you set at the factory is what you get. That keeps the part simple for panel builders who want a known coordination curve without field-adjustment risk. The breaker holds its full 100 A rating from 40 °C through 50 °C, then begins to derate: 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C. No washdown rating; keep this behind a gland plate or enclosure door in wet environments. The auxiliary contact block is factory-installed; the order code for the integrated auxiliary trip module is 3VA9608-0BB11 if you need a spare or replacement. For compliance documentation: the SENTRON 3VA series carries UL 489, CSA C22.2 No. 5, and IEC 60947-2 certifications. RoHS and REACH declarations are available through Siemens Industry Online Support. The 76.2 mm width is a standard 3-pole MCCB footprint — three 25.4 mm pole centers — so it fits existing bus-bar and lug layouts without re-drilling. Depth of 70 mm leaves clearance for rear-connected bus stabs or plug-in bases in switchgear.","metaTitle":"Siemens 3VA1110-5ED32-0BH0 SENTRON MCCB, 100 A, 3-Pole, TM21","metaDescription":"Siemens 3VA1110-5ED32-0BH0 SENTRON molded case circuit breaker, 100 A rated, 3-pole, TM210 release, 187 kA at 240 V. Active production, sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"75.6 kA","at 690 V":"17 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96 A","at 60 °C":"94 A","at 65 °C":"92 A","at 70 °C":"90 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB11","Design of the overcurrent release":"TM210","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 000 A","Adjustable response value current / li min.":"1 000 A","Adjustable response value current / lr min.":"100 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"3","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=47991&mlfb=3VA1110-5ED32-0BH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1110-5ED32-0BH0/alternatives.json"},"ai":{"faq":[{"question":"What is 3VA1110-5ED32-0BH0's listed depth?","answer":"The depth is 70 mm. That measurement is from the mounting surface to the front face of the breaker — important for enclosure depth clearance when using rear-connected bus bars or plug-in bases."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1110-5ED32-0BH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1110-5ED32-0BH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}