{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1110-5ED32-0HA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1110-5ED32-0HA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1110-5ED32-0HA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1110-5ED32-0HA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1110-5ED32-0HA0, molded case circuit breaker, 3-pole, 100 A rated continuous current, line protection, TM210 overcurrent release, 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, 17 kA at 690 V, shunt trip (STL), IP40 front, 70 mm depth, 76.2 mm width, 130 mm height.","salesMarkdown":"It carries a rated insulation voltage of 800 V and delivers interrupting capacities of 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 690 V — per the datasheet, these are the short-circuit ratings that define its fault-clearing capability at each voltage level. No undervoltage release, no auxiliary contact version, no communication function, no phase failure detection, and no ground fault monitoring are included on this variant. At 55 °C it derates to 96 A, at 60 °C to 94 A, at 65 °C to 92 A, and at 70 °C to 90 A. ## Physical integration and protection Protection class on the front is IP40. No trip indicator is fitted. The voltage trigger is present.","metaTitle":"Siemens 3VA1110-5ED32-0HA0 SENTRON MCCB, 100 A, 3-Pole, 187","metaDescription":"Siemens SENTRON 3VA1110-5ED32-0HA0 molded case circuit breaker, 100 A rated continuous current, 3-pole, line protection, 187 kA at 240 V. Current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"75.6 kA","at 690 V":"17 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96 A","at 60 °C":"94 A","at 65 °C":"92 A","at 70 °C":"90 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL30","Design of the overcurrent release":"TM210","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 000 A","Adjustable response value current / li min.":"1 000 A","Adjustable response value current / lr min.":"100 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LI","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=507897&mlfb=3VA1110-5ED32-0HA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1110-5ED32-0HA0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA1110-5ED32-0HA0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What is the closest functional second-source for 3VA1110-5ED32-0HA0?","answer":"The peer 3VA1110-5EE32-0JA0 is a functional alternative within the same SENTRON 3VA family, but the 3VA1110-5ED32-0HA0 carries a TM210 overcurrent release and a shunt trip (STL), while the peer may differ in release design or auxiliary options — verify the specific release and trip configuration before substituting."},{"question":"What is 3VA1110-5ED32-0HA0's listed depth?","answer":"The depth is 70 mm."},{"question":"What is 3VA1110-5ED32-0HA0's listed width?","answer":"The width is 76.2 mm."},{"question":"Will 3VA1110-5ED32-0HA0 drop into a panel specified around 3VA1110-5EE32-0JA0 without rewiring?","answer":"Both breakers share the same SENTRON 3VA platform and the same 3-pole form factor, so the physical footprint and mounting are identical. The wiring interface is the same, but the release and auxiliary trip configuration differ — the 3VA1110-5ED32-0HA0 uses a TM210 thermal-magnetic release with a shunt trip (STL), while the peer may have a different release or no shunt trip. No rewiring is needed for the power circuit, but the control wiring for the shunt trip must be verified."},{"question":"What compliance documentation does Siemens provide for 3VA1110-5ED32-0HA0?","answer":"The evidence does not list specific compliance documentation (RoHS, REACH, UL, IEC) for this order code. Standard Siemens SENTRON MCCBs typically carry IEC 60947-2 and UL 489 certifications, but confirm the exact documentation with the supplier at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1110-5ED32-0HA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1110-5ED32-0HA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}