{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1110-5ED32-0JC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1110-5ED32-0JC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1110-5ED32-0JC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1110-5ED32-0JC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1 IEC frame 160, 3-pole, breaking capacity class M, Icu=55 kA @ 415 V, TM210 thermal-magnetic trip, fixed Ir=100 A, shunt trip STL 110-127 V DC/AC, 2 HQ auxiliary switches.","salesMarkdown":"## What the 55 kA breaking capacity means for your panel The 3VA1110-5ED32-0JC0 is a 3-pole IEC frame 160 circuit breaker with a 55 kA interrupting capacity at 415 V AC — class M in the 3VA1 line. The TM210 thermal-magnetic trip unit gives fixed overload protection at Ir=100 A and fixed short-circuit protection at Ii=10 x In (1000 A), so the breaker is sized for a 100 A continuous load with a 10x magnetic pickup for motor-start or transformer inrush. ## Integrated accessories: shunt trip and auxiliary switches Factory-fitted with a shunt trip (STL) rated 110-127 V DC and AC 50/60 Hz, plus two HQ auxiliary switches. The shunt trip lets a remote emergency-stop or PLC-based trip signal open the breaker without an operator at the handle — common in safety circuits or remote-disconnect panels. The two HQ aux switches provide independent NO/NC status feedback to a DCS, PLC, or status lamp. Because these are factory-installed, you avoid field-wiring an accessory kit into the breaker's internal mechanism.","metaTitle":"Siemens 3VA1110-5ED32-0JC0 3VA1 IEC Frame 160, 55 kA @ 415 V","metaDescription":"Siemens 3VA1110-5ED32-0JC0 circuit breaker, IEC frame 160, breaking capacity class M, Icu=55 kA @ 415 V, 3-pole, TM210 thermal-magnetic trip, fixed Ir=100 A, shunt trip 110-127 V,","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=196885&mlfb=3VA1110-5ED32-0JC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1110-5ED32-0JC0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA1110-5ED32-0JC0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of this breaker?","answer":"The 3VA1110-5ED32-0JC0 has an Icu of 55 kA at 415 V AC, which is the class M breaking capacity for the IEC frame 160 platform."},{"question":"What accessories are factory-installed on this breaker?","answer":"It includes a shunt trip (STL) rated 110-127 V DC/AC and two HQ auxiliary switches, all factory-fitted."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1110-5ED32-0JC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1110-5ED32-0JC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}