{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1110-5ED32-0JH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1110-5ED32-0JH0","canonicalUrl":"https://aoctrl.com/siemens/3VA1110-5ED32-0JH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1110-5ED32-0JH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1110-5ED32-0JH0, molded case circuit breaker, 3-pole, 100 A at 40 °C, interrupting rating 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V.","salesMarkdown":"It carries a 187 kA interrupting rating at 240 V, 121 kA at 415 V, and 75.6 kA at 440 V — the interrupting capacity drops to 17 kA at 500 V and 690 V. This is a current-production part (lifecycle stage: current). The 100 A rating holds flat from 40 °C to 50 °C, then derates to 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. At 240 V it clears 187 kA, enough for high-capacity transformer secondaries; at 415 V it clears 121 kA, typical for industrial distribution. The shunt trip allows remote tripping, useful for emergency-stop circuits or interlocking. The trip alarm switch signals a fault condition separately from the auxiliary position feedback. Power loss is 25 W maximum at rated current — factor that into the enclosure thermal budget, especially in a multi-breaker lineup. The 3VA1110-5ED32-0JH0 measures 130 mm high, 76.2 mm wide, 70 mm deep. The 3-pole footprint matches standard SENTRON 3VA panel cutouts — no rewiring needed if swapping from a 3VA1110-5ED36-0AC0, since the mounting centers and terminal layout are identical within the same frame size.","metaTitle":"Siemens 3VA1110-5ED32-0JH0 SENTRON MCCB, 100 A, 3-Pole, 187","metaDescription":"Siemens SENTRON 3VA1110-5ED32-0JH0 molded case circuit breaker, 100 A rated at 40 °C, 3-pole, 187 kA interrupting at 240 V. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"75.6 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"98 A","at 60 °C":"96 A","at 65 °C":"94 A","at 70 °C":"91 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"25 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA11105ED320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL32","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=424269&mlfb=3VA1110-5ED32-0JH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1110-5ED32-0JH0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1110-5ED32-0JH0 and get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability."},{"question":"What is the closest functional second-source for 3VA1110-5ED32-0JH0?","answer":"The 3VA1110-5ED36-0AC0 is a peer within the same SENTRON 3VA family. Both are 3-pole MCCBs with identical frame dimensions (130 x 76.2 x 70 mm) and the same auxiliary switch configuration. The key difference is the current rating: the -5ED32-0JH0 is rated 100 A, while the -5ED36-0AC0 is rated 125 A. The interrupting ratings and thermal derating curves also differ — verify the system fault current and load before substituting."},{"question":"Will 3VA1110-5ED32-0JH0 drop into a panel specified for 3VA1110-5ED36-0AC0?","answer":"Yes — both are the same frame size (130 x 76.2 x 70 mm) with the same mounting pattern and terminal layout. No rewiring or panel modification is needed."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1110-5ED32-0JH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1110-5ED32-0JH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}