{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1110-5ED36-0AC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1110-5ED36-0AC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1110-5ED36-0AC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1110-5ED36-0AC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1110-5ED36-0AC0, molded case circuit breaker, 3-pole, 100 A rated current at 40 °C, breaking capacity 187 kA at 240 V, TM210 thermal-magnetic release, 2 auxiliary switches HQ.","salesMarkdown":"The Siemens 3VA1110-5ED36-0AC0 is a SENTRON molded case circuit breaker (MCCB) rated for 100 A continuous at 40 °C, with a 3-pole configuration and a TM210 thermal-magnetic overcurrent release. Its interrupting capacity hits 187 kA at 240 V AC, dropping to 121 kA at 415 V and 75.6 kA at 440 V — numbers that tell you it's built for high-fault industrial distribution, not light commercial service. At 100 A continuous, this MCCB carries a full 3-phase load without derating up to 50 °C; above that it drops to 98 A at 55 °C and 91 A at 70 °C. Dimensions are 70 mm deep, 76.2 mm wide, 130 mm tall — a standard SENTRON 3VA footprint that fits the existing mounting base and busbar system. ## Auxiliary switching and release options The basic switch assembly is order code 3VA11105ED360AA0, which is the internal mechanism; you're buying the complete breaker here.","metaTitle":"Siemens 3VA1110-5ED36-0AC0 SENTRON MCCB, 100 A, 3-Pole, 187","metaDescription":"Siemens SENTRON 3VA1110-5ED36-0AC0 molded case circuit breaker, 100 A at 40 °C, 3-pole, 187 kA breaking at 240 V. TM210 release, 2 HQ aux switches. Current production. Quoted to or","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"75.6 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"98 A","at 60 °C":"96 A","at 65 °C":"94 A","at 70 °C":"91 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"25 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA11105ED360AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1437974&mlfb=3VA1110-5ED36-0AC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1110-5ED36-0AC0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of this MCCB at different voltages?","answer":"187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at both 500 V and 690 V."},{"question":"Where can I buy 3VA1110-5ED36-0AC0 and how is it quoted?","answer":"We source this through independent distribution and quote it to order against an RFQ. Availability and current pricing are confirmed at quote time."},{"question":"What type of overcurrent release does this breaker have?","answer":"A TM210 thermal-magnetic release — fixed thermal at 100 A, adjustable magnetic pickup."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1110-5ED36-0AC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1110-5ED36-0AC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}