{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1110-5EE32-0AH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1110-5EE32-0AH0","canonicalUrl":"https://aoctrl.com/siemens/3VA1110-5EE32-0AH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1110-5EE32-0AH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1110-5EE32-0AH0, molded case circuit breaker, 3-pole, 100 A, TM220 release, 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, 17 kA at 690 V, IP40 front, 70 x 76.2 x 130 mm.","salesMarkdown":"## Line protection MCCB with TM220 release The interrupting capacity at 240 V reaches 187 kA, at 415 V it is 121 kA, at 440 V it is 75.6 kA, and at 690 V it is 17 kA — these figures define the maximum fault current the breaker can safely clear at each voltage level, which is the primary selection criterion for panel coordination studies. The TM220 release is adjustable; the thermal time delay tr max is set at 1 s. Above that, derate linearly: 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C.","metaTitle":"Siemens 3VA1110-5EE32-0AH0 SENTRON MCCB, 100 A, 187 kA at 24","metaDescription":"Siemens SENTRON 3VA1110-5EE32-0AH0 molded case circuit breaker, 100 A rated, 187 kA at 240 V. TM220 release, 3-pole, IP40 front. Current lifecycle. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"75.6 kA","at 690 V":"17 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96 A","at 60 °C":"94 A","at 65 °C":"92 A","at 70 °C":"90 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"without auxiliaryrelease","Ground fault monitoring version":"Without","Design of the overcurrent release":"TM220","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 000 A","Adjustable response value current / li min.":"1 000 A","Adjustable response value current / lr min.":"70 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"3","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=320377&mlfb=3VA1110-5EE32-0AH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1110-5EE32-0AH0/alternatives.json"},"ai":{"faq":[{"question":"What is 3VA1110-5EE32-0AH0's listed depth (70 mm) on this component line?","answer":"The depth is 70 mm, with a width of 76.2 mm and a height of 130 mm."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1110-5EE32-0AH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1110-5EE32-0AH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}