{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1110-5EF36-0DA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1110-5EF36-0DA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1110-5EF36-0DA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1110-5EF36-0DA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1110-5EF36-0DA0, molded case circuit breaker, 3-pole, 100 A, 187 kA at 240 V, line protection, undervoltage release, TM240 overcurrent release.","salesMarkdown":"## Rated continuous current and breaking capacity Its breaking capacity reaches 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 690 V — figures that govern its ability to safely interrupt fault currents without upstream damage. Above that, derating applies: 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C. The 3VA1110-5EF36-0DA0 measures 70 mm deep, 76.2 mm wide, and 130 mm high. Front IP40 protection keeps dust and tools out of the mechanism. The 3-pole footprint matches the standard SENTRON 3VA mounting pattern — it drops into a panel cutout or DIN-rail adapter without modification. The absence of an auxiliary contact version means no add-on signaling block is pre-installed; if remote status is needed, the integrated auxiliary trip port (order code 3VA9608-0BB25) accepts a field-installed module.","metaTitle":"Siemens 3VA1110-5EF36-0DA0 SENTRON MCCB, 100 A, 187 kA at 24","metaDescription":"Siemens 3VA1110-5EF36-0DA0 SENTRON molded case circuit breaker, 100 A rated continuous current, 187 kA breaking capacity at 240 V. Line protection, undervoltage release. Available","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"75.6 kA","at 690 V":"17 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96 A","at 60 °C":"94 A","at 65 °C":"92 A","at 70 °C":"90 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB25","Design of the overcurrent release":"TM240","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 000 A","Adjustable response value current / li min.":"500 A","Adjustable response value current / lr min.":"70 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LI","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1.5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=191267&mlfb=3VA1110-5EF36-0DA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1110-5EF36-0DA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1110-5EF36-0DA0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What are the key ratings of 3VA1110-5EF36-0DA0?","answer":"Rated continuous current Iu is 100 A, breaking capacity reaches 187 kA at 240 V, rated insulation voltage Ui is 800 V, and the overcurrent release is TM240. The breaker includes an undervoltage release."},{"question":"What is the depth of 3VA1110-5EF36-0DA0?","answer":"The depth is 70 mm, width is 76.2 mm, and height is 130 mm."},{"question":"Will 3VA1110-5EF36-0DA0 drop into a panel specified for 3VA1110-5EE32-0JA0?","answer":"Both are 3-pole SENTRON 3VA frame breakers with the same 70 mm depth, 76.2 mm width, and 130 mm height, so the mechanical fit is identical. The difference lies in the overcurrent release and breaking capacity — the -5EF36-0DA0 uses a TM240 release with higher interrupting ratings, while the -5EE32-0JA0 uses a different release. No rewiring is needed for the mounting footprint, but verify the release settings match the application."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1110-5EF36-0DA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1110-5EF36-0DA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}