{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1110-5MH36-0JC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1110-5MH36-0JC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1110-5MH36-0JC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1110-5MH36-0JC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1 IEC frame 160, breaking capacity class M, Icu=55kA @ 415V, 3-pole, starter protection TM120M, In=100A, shunt trip 110-127V DC/AC, 2 auxiliary switches HQ, clamp connection.","salesMarkdown":"The Siemens 3VA1110-5MH36-0JC0 is a 3-pole IEC frame 160 molded-case circuit breaker rated 100 A continuous, with a 55 kA breaking capacity at 415 V (class M). For a 415 V distribution panel, that puts it well above typical utility fault levels, so you get selectivity headroom without upsizing the frame. The TM120M trip unit is a thermal-magnetic, fixed-trip design with adjustable short-circuit pickup (Ii = 5…15 × In). It does not include overload protection — this variant is intended for starter protection, where the upstream overload relay handles the thermal curve and the breaker provides only short-circuit interruption. The adjustable magnetic pickup lets you dial in motor inrush without nuisance tripping. Clamp terminals accept copper or aluminum conductors up to the frame rating. The shunt trip (STL) operates on 110–127 V DC or AC 50/60 Hz, letting you integrate remote trip from an E-stop or safety relay. Two HQ auxiliary switches provide status feedback to the PLC or annunciator panel — one for the main contacts, one for the trip signal.","metaTitle":"Siemens 3VA1110-5MH36-0JC0 Circuit Breaker, 100A, 55kA @ 415","metaDescription":"Siemens 3VA1110-5MH36-0JC0 IEC frame 160 MCCB, 100A, 55kA breaking capacity at 415V, starter protection TM120M, shunt trip, 2 aux switches. Current lifecycle. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=383810&mlfb=3VA1110-5MH36-0JC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1110-5MH36-0JC0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of this breaker?","answer":"Icu = 55 kA at 415 V AC, breaking capacity class M per IEC 60947-2."},{"question":"Does this breaker include overload protection?","answer":"No — this is a starter-protection variant without overload protection. The TM120M trip unit provides only short-circuit protection with adjustable magnetic pickup (Ii = 5…15 × In). An external overload relay is required for motor thermal protection."},{"question":"How do I get pricing and availability for the 3VA1110-5MH36-0JC0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1110-5MH36-0JC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1110-5MH36-0JC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}