{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1110-6ED36-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1110-6ED36-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1110-6ED36-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1110-6ED36-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1110-6ED36-0AA0, 3-pole molded case circuit breaker, 100 A rated current, TM210 thermal-magnetic release, line protection version, 70 mm depth.","salesMarkdown":"## Breaking capacity and what it means for your fault-current study The 3VA1110-6ED36-0AA0: This MCCB carries a 220 kA interrupting rating at 240 VAC, dropping to 154 kA at 415 VAC, 121 kA at 440 VAC, and 17 kA at both 500 VAC and 690 VAC. At 690 V, the 17 kA rating is the limiting figure; if your system's prospective short-circuit current exceeds that, you need a current-limiting upstream breaker or a higher-rated frame. ## Thermal derating — don't size at the nameplate alone Rated 100 A at 40 °C, the breaker holds that current up to 50 °C, then begins a gradual derating curve: 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. The TM210 release's thermal element responds to the actual current through the breaker, so an undersized conductor or an overestimated continuous load at elevated temperature can cause nuisance tripping. At 70 mm deep, 76.2 mm wide, and 130 mm tall, this 3-pole MCCB fits standard SENTRON mounting footprints. The front face carries an IP40 protection class — suitable for general-purpose panel mounting where no washdown or dust ingress is expected.","metaTitle":"Siemens 3VA1110-6ED36-0AA0 SENTRON MCCB, 100 A, 3-Pole, 220","metaDescription":"Siemens SENTRON 3VA1110-6ED36-0AA0 molded case circuit breaker, 100 A, 3-pole, TM210 release. Breaking capacity 220 kA at 240 VAC. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"121 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"98 A","at 60 °C":"96 A","at 65 °C":"94 A","at 70 °C":"91 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Product version":"Line protection","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"25 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","operating voltage / at AC / rated value":"690 V","Max. rated operational voltage Ue with DC":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Switching Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1,5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/5d63a991027429944096267eaac945e7.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=269933&mlfb=3VA1110-6ED36-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1110-6ED36-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA1110-6ED36-0AA0 at different voltages?","answer":"The interrupting rating is 220 kA at 240 VAC, 154 kA at 415 VAC, 121 kA at 440 VAC, and 17 kA at both 500 VAC and 690 VAC. The 690 V figure is the limiting value for high-voltage applications."},{"question":"What is the current rating and derating for 3VA1110-6ED36-0AA0?","answer":"Rated 100 A continuous at 40 °C, holding that value through 50 °C. Derates to 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. Size your continuous load at the derated value for the expected panel ambient."},{"question":"Will 3VA1110-6ED36-0AA0 drop into a panel specified for 3VA1110-5ED36-0AA0?","answer":"Both are 3-pole SENTRON 3VA frame breakers with the same 70 mm depth, 76.2 mm width, and 130 mm height. The -6ED36 variant carries a TM210 release; the -5ED36 variant uses a different release code. Mounting footprint and bus-bar spacing are identical, so mechanical fit is the same. Verify the release curve matches your application before substituting."},{"question":"Where can I buy 3VA1110-6ED36-0AA0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1110-6ED36-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1110-6ED36-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}