{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1110-6ED36-0AH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1110-6ED36-0AH0","canonicalUrl":"https://aoctrl.com/siemens/3VA1110-6ED36-0AH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1110-6ED36-0AH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1110-6ED36-0AH0, molded case circuit breaker, 3-pole, 100 A, TM210 thermal-magnetic release, 220 kA at 240 V, line protection.","salesMarkdown":"At 415 V the rating is still 154 kA, and at 440 V it holds 121 kA, so this breaker stays selective with downstream devices across a wide voltage band. The interrupting capacity drops to 17 kA at 500 V and 690 V, which is still adequate for most 480 V and 600 V class installations but worth noting if your system runs above 480 V and the fault current exceeds that figure. The breaker carries 100 A from 40 °C through 50 °C without derating; at 55 °C it drops to 98 A, at 60 °C to 96 A, at 65 °C to 94 A, and at 70 °C to 91 A. That 76.2 mm width is three 25.4 mm pole spaces — standard for a 3-pole MCCB in a Siemens or generic distribution panel. The 70 mm depth means it fits shallow enclosures where a deeper frame would hit the backplate or gland plate. Mounting is via the standard SENTRON base plate or DIN rail adapter (not included); the TM210 release is factory-set and non-interchangeable, so no field calibration is needed. The trip indicator gives a visual flag when the breaker has opened on fault — useful for troubleshooting without opening the panel door.","metaTitle":"Siemens 3VA1110-6ED36-0AH0 SENTRON MCCB, 100 A, 3-Pole, 220","metaDescription":"Siemens 3VA1110-6ED36-0AH0 SENTRON molded case circuit breaker, 100 A, 3-pole, TM210 release, 220 kA at 240 V. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"121 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"98 A","at 60 °C":"96 A","at 65 °C":"94 A","at 70 °C":"91 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"Yes","Number Of Poles":"3","Product version":"Line protection","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"25 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA11106ED360AA0","Courant permanent assigné Iu":"100 A","Design Of The Auxiliary Release":"without auxiliaryrelease","Ground-Fault Monitoring Version":"Without","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Adjustable response value current / li max.":"1 000 A","Adjustable response value current / li min.":"1 000 A","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"H","Max. rated operational current of the frame size":"160 A","Mechanical Service Life (Switching Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1.5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1353872&mlfb=3VA1110-6ED36-0AH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1110-6ED36-0AH0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1110-6ED36-0AH0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What are the key ratings for 3VA1110-6ED36-0AH0?","answer":"Rated 100 A continuous at 40 °C, 3-pole, TM210 thermal-magnetic release. Interrupting capacity is 220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and 17 kA at 500 V and 690 V. Rated insulation voltage Ui is 800 V. Dimensions are 76.2 mm wide × 130 mm tall × 70 mm deep."},{"question":"What is the closest functional alternative to 3VA1110-6ED36-0AH0?","answer":"The 3VA1010-2ED32-0JA0 is a sibling in the same SENTRON 3VA platform but uses a different release and interrupting rating. The 3VA1110-6ED36-0AH0 carries the TM210 release and the higher 220 kA at 240 V interrupting capacity; the 3VA1010-2ED32-0JA0 has a different release and lower interrupting rating. They share the same frame size and mounting footprint, so a panel designed for one can accept the other without rewiring, but the protection curve and SCCR must be verified against the system fault study."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1110-6ED36-0AH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1110-6ED36-0AH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}