{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1110-6EF32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1110-6EF32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1110-6EF32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1110-6EF32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1110-6EF32-0AA0, 3-pole molded case circuit breaker, 100 A, TM240 thermal-magnetic release, line protection, breaking capacity 220 kA at 240 V AC.","salesMarkdown":"The Siemens 3VA1110-6EF32-0AA0 is a 3-pole SENTRON molded case circuit breaker rated for 100 A continuous at 40 °C, with a TM240 thermal-magnetic overcurrent release designed for line protection. Its breaking capacity reaches 220 kA at 240 V AC, 154 kA at 415 V, and 121 kA at 440 V — sufficient for high-fault utility feeds and transformer secondaries. The breaker holds its full 100 A rating from 40 °C through 50 °C, then derates linearly to 91 A at 70 °C. Front protection is IP40; the enclosure must provide the rest of the ingress rating.","metaTitle":"Siemens 3VA1110-6EF32-0AA0 SENTRON MCCB, 100A, 220kA at 240V","metaDescription":"Siemens 3VA1110-6EF32-0AA0 SENTRON molded case circuit breaker, 3-pole, 100A, TM240 release, breaking capacity 220kA at 240V AC. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"121 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"98 A","at 60 °C":"96 A","at 65 °C":"94 A","at 70 °C":"91 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"25 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM240","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/054c479b19a050508d8602e0150aa8e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=74793&mlfb=3VA1110-6EF32-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1110-6EF32-0AA0/alternatives.json"},"ai":{"faq":[{"question":"How do I get pricing and availability for 3VA1110-6EF32-0AA0?","answer":"Submit an RFQ through this listing. The part is sourced to order; current pricing and stock status are confirmed at quote time."},{"question":"Will 3VA1110-6EF32-0AA0 drop into a panel specified for 3VA1110-5ED32-0AA0?","answer":"Both are 3-pole 100 A SENTRON MCCBs in the same 130 x 76.2 x 70 mm footprint, so the physical swap is straightforward. The difference is the overcurrent release: the -6EF32 carries a TM240 thermal-magnetic release, while the -5ED32 uses a different release variant. Verify the trip curve matches your coordination study before the swap."},{"question":"What compliance documentation does this breaker carry?","answer":"As a Siemens SENTRON product, it is designed to meet IEC 60947-2 and UL 489 standards. RoHS and REACH declarations are available through Siemens Industry Online Support. The front IP40 rating is stated on the nameplate."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1110-6EF32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1110-6EF32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}