{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1110-6EF32-0KC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1110-6EF32-0KC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1110-6EF32-0KC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1110-6EF32-0KC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1 IEC frame 160 circuit breaker, breaking capacity class H, Icu=70kA @ 415V, 3-pole, line protection TM240, ATAM, In=100A, overload Ir=70A...100A, short-circuit Ii=5...10 x In, nut keeper kit, shunt trip (STL) 220-250V DC / 208-277V AC, 2 auxiliary switches HQ.","salesMarkdown":"The Siemens 3VA1110-6EF32-0KC0 is a 3-pole IEC frame 160 molded-case circuit breaker in breaking capacity class H, rated Icu=70kA at 415 V AC. It ships with a TM240 thermal-magnetic trip unit set for In=100 A, overload protection adjustable Ir=70...100 A, and short-circuit pickup Ii=5...10 x In. The factory-fitted accessories include a shunt trip (STL) rated 220-250 V DC / 208-277 V AC, two HQ auxiliary switches, and a nut keeper kit — no loose hardware to chase down mid-install. The TM240 trip unit gives a thermal curve for overloads and a magnetic instantaneous for shorts; the adjustable Ir (70-100 A) lets you match the cable or load without swapping the trip pack. The shunt trip coil accepts both DC and AC control voltages, so it integrates into either a 220 V DC trip circuit or a 208-277 V AC emergency-off string.","metaTitle":"Siemens 3VA1110-6EF32-0KC0 Circuit Breaker, 70kA @ 415V, 100","metaDescription":"Siemens 3VA1110-6EF32-0KC0 IEC frame 160 circuit breaker, class H Icu=70kA @ 415V, 3-pole, TM240, In=100A, shunt trip, 2 aux switches. Current production lifecycle. Quoted to order","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=529671&mlfb=3VA1110-6EF32-0KC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1110-6EF32-0KC0/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for 3VA1110-6EF32-0KC0?","answer":"IEC frame 160, class H breaking capacity Icu=70kA @ 415V, 3-pole, TM240 thermal-magnetic trip, In=100A, overload Ir=70A...100A, short-circuit Ii=5...10 x In. Includes shunt trip (STL) 220-250V DC / 208-277V AC and 2 HQ auxiliary switches."},{"question":"How do I get pricing and availability for 3VA1110-6EF32-0KC0?","answer":"Submit an RFQ — this part is sourced and quoted to order through independent distribution, with availability and current pricing confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1110-6EF32-0KC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1110-6EF32-0KC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}