{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1110-6EF36-0AE0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1110-6EF36-0AE0","canonicalUrl":"https://aoctrl.com/siemens/3VA1110-6EF36-0AE0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1110-6EF36-0AE0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1110-6EF36-0AE0, molded case circuit breaker, 3-pole, 100 A rated continuous current Iu, TM240 thermal-magnetic trip unit, 220 kA breaking capacity at 240 V, 4 auxiliary switches HQ, IP40 front, active.","salesMarkdown":"The Siemens 3VA1110-6EF36-0AE0 is a 3-pole SENTRON molded case circuit breaker rated for 100 A continuous current (Iu) with a TM240 thermal-magnetic trip unit — the '240' indicates the fixed thermal pickup at 100% of rated current, so it holds 100 A continuously and trips on overload above that threshold without field adjustment. The 220 kA interrupting rating at 240 V tells you this breaker can safely clear a fault up to that level on a 240 V line; at 415 V it still handles 154 kA, and at 690 V it's rated 17 kA. That's a high-interrupting-capacity (HIC) frame — sized for transformer secondaries or large motor branch circuits where fault current runs high. The 4 auxiliary switches (HQ type) give you four form-C contacts for remote status indication — useful for PLC feedback on a body-shop weld line where you need to know the breaker state without walking the panel. ## Deployment context Panel footprint is 76.2 mm wide by 130 mm high by 70 mm deep — standard 3-pole MCCB envelope for DIN-rail or screw-mount backplate.","metaTitle":"Siemens 3VA1110-6EF36-0AE0 SENTRON MCCB, 100 A, 220 kA at 24","metaDescription":"Siemens SENTRON 3VA1110-6EF36-0AE0 molded case circuit breaker, 100 A rated, 220 kA at 240 V. TM240 trip unit, 4 auxiliary switches. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"121 kA","at 690 V":"17 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96 A","at 60 °C":"94 A","at 65 °C":"92 A","at 70 °C":"90 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"4 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"without auxiliaryrelease","Ground fault monitoring version":"Without","Design of the overcurrent release":"TM240","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 000 A","Adjustable response value current / li min.":"500 A","Adjustable response value current / lr min.":"70 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"4","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1.5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=498741&mlfb=3VA1110-6EF36-0AE0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1110-6EF36-0AE0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA1110-6EF36-0AE0?","answer":"Submit an RFQ through this listing. Pricing and stock are confirmed at quote time through independent distribution channels."},{"question":"What is the breaking capacity at 415 V?","answer":"The 3VA1110-6EF36-0AE0 is rated 154 kA at 415 V."},{"question":"Does this MCCB include an undervoltage release?","answer":"No, this variant has no undervoltage release and no auxiliary release fitted."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1110-6EF36-0AE0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1110-6EF36-0AE0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}