{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1110-6EF36-0AH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1110-6EF36-0AH0","canonicalUrl":"https://aoctrl.com/siemens/3VA1110-6EF36-0AH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1110-6EF36-0AH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1110-6EF36-0AH0, 3-pole molded case circuit breaker, 100 A rated continuous current, TM240 thermal-magnetic release, 220 kA breaking capacity at 240 V.","salesMarkdown":"The Siemens 3VA1110-6EF36-0AH0 is a SENTRON molded case circuit breaker (MCCB) in a 3-pole configuration, rated for 100 A continuous current (Iu) with a TM240 thermal-magnetic overcurrent release. Its breaking capacity hits 220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and 17 kA at 690 V — numbers that tell you this breaker is sized for high-fault industrial distribution, not light commercial subfeeds. The 70 mm depth and 76.2 mm width fit standard DIN-rail or panel-mount layouts, and the IP40 front protection means it's fine in a clean indoor enclosure but not for washdown zones. This MCCB holds 100 A flat from 40 °C through 50 °C ambient. At 55 °C it derates to 96 A, at 60 °C to 94 A, at 65 °C to 92 A, and at 70 °C to 90 A. The 800 V rated insulation voltage (Ui) gives headroom for 690 V line-to-line systems, but the 17 kA SCCR at that voltage is the limiting factor for fault duty. Mechanical endurance is 15,000 cycles, which is standard for a line-protection MCCB in a distribution board that sees infrequent switching.","metaTitle":"Siemens 3VA1110-6EF36-0AH0 MCCB, 100 A, 220 kA at 240 V","metaDescription":"Siemens SENTRON 3VA1110-6EF36-0AH0 molded case circuit breaker, 3-pole, 100 A, TM240 release, 220 kA at 240 V. Current lifecycle stage. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"121 kA","at 690 V":"17 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96 A","at 60 °C":"94 A","at 65 °C":"92 A","at 70 °C":"90 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"without auxiliaryrelease","Ground fault monitoring version":"Without","Design of the overcurrent release":"TM240","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 000 A","Adjustable response value current / li min.":"500 A","Adjustable response value current / lr min.":"70 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"3","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1.5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/991773cac324ce917e09d6934f7fb4f6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=447122&mlfb=3VA1110-6EF36-0AH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1110-6EF36-0AH0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA1110-6EF36-0AH0 at different voltages?","answer":"220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and 17 kA at 690 V. These are the interrupting ratings that govern selectivity and SCCR coordination in the distribution panel."},{"question":"Where can I buy 3VA1110-6EF36-0AH0 and how is it quoted?","answer":"This part is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time — no stock count or price is published here."},{"question":"Will 3VA1110-6EF36-0AH0 drop into a panel specified for 3VA1110-5EE32-0JA0?","answer":"Both are 3-pole, 100 A SENTRON MCCBs in the same 3VA platform, so the physical footprint (70 mm depth, 76.2 mm width, 130 mm height) is identical. The difference is in the overcurrent release: this unit uses a TM240 thermal-magnetic release, while the -5EE32 variant uses a different release curve. Verify the trip settings match your coordination study before swapping."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1110-6EF36-0AH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1110-6EF36-0AH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}