{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1110-6EF36-0HA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1110-6EF36-0HA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1110-6EF36-0HA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1110-6EF36-0HA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1110-6EF36-0HA0, Molded case circuit breaker, 3-pole, 100 A, TM240 overcurrent release, 220 kA at 240 V, line protection.","salesMarkdown":"The Siemens SENTRON 3VA1110-6EF36-0HA0 is a 3-pole molded case circuit breaker rated for 100 A continuous current at 40 °C, with a TM240 thermal-magnetic overcurrent release. The TM240 release means the thermal element is calibrated for a 100 A frame with a fixed magnetic trip threshold. For a site electrical engineer working selectivity tables, this breaker sits in the SENTRON 3VA family where downstream MCBs (SENTRON 5SL or 5SY series) coordinate cleanly up to the listed interrupting levels. The 15 000 mechanical endurance cycles (latching) are typical for a distribution MCCB — not a switching device, but rated for occasional manual isolation during maintenance. ## Panel fit and mounting constraints At 76.2 mm wide (roughly 3 inches) and 70 mm deep, this breaker fits standard SENTRON 3VA mounting footprints. No auxiliary contacts or shunt trip are integrated, but the design accepts the 3VA9688-0BL30 shunt trip (STL) as a field-addable accessory if remote tripping is needed later.","metaTitle":"Siemens 3VA1110-6EF36-0HA0 SENTRON MCCB, 100 A, 220 kA at 24","metaDescription":"Siemens SENTRON 3VA1110-6EF36-0HA0 molded case circuit breaker, 100 A rated, 220 kA at 240 V, TM240 release, line protection. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"121 kA","at 690 V":"17 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96 A","at 60 °C":"94 A","at 65 °C":"92 A","at 70 °C":"90 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL30","Design of the overcurrent release":"TM240","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 000 A","Adjustable response value current / li min.":"500 A","Adjustable response value current / lr min.":"70 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LI","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1.5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=336220&mlfb=3VA1110-6EF36-0HA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1110-6EF36-0HA0/alternatives.json"},"ai":{"faq":[{"question":"What is the interrupting capacity of 3VA1110-6EF36-0HA0 at 415 V?","answer":"154 kA at 415 V, with 220 kA at 240 V and 121 kA at 440 V."},{"question":"Where can I buy 3VA1110-6EF36-0HA0 and how is it quoted?","answer":"Sourced and quoted to order against an RFQ through independent distribution, with availability and current pricing confirmed at quote time."},{"question":"Does this breaker include an auxiliary contact or shunt trip?","answer":"No auxiliary contacts are included, but the design accepts the 3VA9688-0BL30 shunt trip (STL) as a field-addable accessory."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1110-6EF36-0HA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1110-6EF36-0HA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}