{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1110-6EF36-0JA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1110-6EF36-0JA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1110-6EF36-0JA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1110-6EF36-0JA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1110-6EF36-0JA0, 3-pole molded case circuit breaker, rated 100 A continuous, TM240 thermal-magnetic release, 220 kA interrupting at 240 V, line protection version.","salesMarkdown":"The Siemens SENTRON 3VA1110-6EF36-0JA0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current at 40 °C, with a TM240 thermal-magnetic overcurrent release. The interrupting ratings are what make this part stand out: 220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and still 17 kA at 690 V. The 70 mm depth and 76.2 mm width match the standard SENTRON 3VA mounting footprint, so it drops into existing panel layouts that already use 3VA breakers. At 55 °C it's 96 A, at 60 °C it's 94 A, at 65 °C it's 92 A, and at 70 °C it's 90 A. That's a gentle slope; you don't lose much headroom even in a hot enclosure. It's a straightforward, reliable overcurrent trip for applications where you don't need selectivity curves or remote signaling. The shunt trip (STL) is built in, so you can remotely open the breaker via a control signal; the auxiliary trip accessory is order code 3VA9688-0BL32 if you need that later. No undervoltage release, no auxiliary contacts, no phase-failure detection — this is a bare-bones line-protection breaker with a high interrupt rating and a shunt trip.","metaTitle":"Siemens 3VA1110-6EF36-0JA0 SENTRON MCCB, 100 A, 220 kA at 24","metaDescription":"Siemens SENTRON 3VA1110-6EF36-0JA0 molded case circuit breaker, 3-pole, 100 A, TM240 release, 220 kA at 240 V. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"121 kA","at 690 V":"17 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96 A","at 60 °C":"94 A","at 65 °C":"92 A","at 70 °C":"90 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"TM240","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 000 A","Adjustable response value current / li min.":"500 A","Adjustable response value current / lr min.":"70 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LI","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1.5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=294396&mlfb=3VA1110-6EF36-0JA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1110-6EF36-0JA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1110-6EF36-0JA0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"Will 3VA1110-6EF36-0JA0 drop into a panel that was specified around 3VA1110-5EE32-0JA0 without rewiring?","answer":"Both are 3-pole SENTRON 3VA breakers with the same 70 mm depth and 76.2 mm width, so the physical footprint and mounting are identical. The key difference is the interrupting rating: this 6EF36 variant carries 220 kA at 240 V versus the 5EE32's lower rating. If the panel's bus bracing and SCCR support the higher interrupt capacity, it's a direct mechanical swap. Verify the shunt trip wiring — both use the same accessory slot, but the release type may differ."},{"question":"What compliance documentation does this brand provide for 3VA1110-6EF36-0JA0?","answer":"Siemens SENTRON 3VA breakers are typically covered by IEC 60947-2 and UL 489 certifications. The reference code per DIN EN 81346-2 is Q. For specific RoHS, REACH, and UL documentation, request the manufacturer's declaration of conformity and the product certificate — these are available from Siemens upon request or through the distributor at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1110-6EF36-0JA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1110-6EF36-0JA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}