{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1110-6EF46-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1110-6EF46-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1110-6EF46-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1110-6EF46-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1110-6EF46-0AA0, molded case circuit breaker, line protection, 4-pole, 100 A rated current, TM240 release, 220 kA at 240 V.","salesMarkdown":"The Siemens SENTRON 3VA1110-6EF46-0AA0 is a 4-pole molded case circuit breaker rated for 100 A continuous at 45 °C and 50 °C, derating to 91 A at 70 °C. Its TM240 thermal-magnetic release gives fixed thermal and adjustable magnetic pickup (up to 1000 A li max), making it a line-protection device for distribution panels feeding motor control centers or general loads. The interrupting capacity is 220 kA at 240 V AC, 154 kA at 415 V, 121 kA at 440 V, and 17 kA at 500 V and 690 V — numbers that tell you this breaker is sized for high-fault locations like transformer secondaries or large switchboards, not for branch circuits with limited fault current. At 70 mm deep, 101.6 mm wide, and 130 mm tall, it fits standard SENTRON 3VA panel cutouts. ## Selectivity and coordination The 4-pole design handles three-phase plus neutral (or a switched neutral in some configurations). The TM240 release is a standard thermal-magnetic curve — not electronic, so no adjustable time-current curve beyond the magnetic pickup range.","metaTitle":"Siemens 3VA1110-6EF46-0AA0 SENTRON MCCB, 100 A, 4-Pole, 220","metaDescription":"Siemens SENTRON 3VA1110-6EF46-0AA0 molded case circuit breaker, 100 A, 4-pole, TM240 release. Rated 220 kA at 240 V, 154 kA at 415 V. Active production, sourced to order. Request q","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"101.6 mm","Height":"130 mm","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"121 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"98 A","at 60 °C":"96 A","at 65 °C":"94 A","at 70 °C":"91 A","Depth [In]":"2.76 in","Width [In]":"4 in","Height [In]":"5.12 in","Number Of Poles":"4","Product version":"Line protection","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"25 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Courant permanent assigné Iu":"100 A","Ground-Fault Monitoring Version":"Without","Tension assignée d'isolement Ui":"800 V","Design Of The Overcurrent Release":"TM240","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","design of the N-conductor protection":"Without","reference code / acc. to IEC 81346-2":"Q","Max. rated operational voltage Ue with DC":"600 V","Product Extension / Optional / Motor Drive":"Yes","Adjustable response value current / li max.":"1 000 A","Adjustable response value current / li min.":"500 A","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Max. rated operational current of the frame size":"160 A","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1.5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e6ad87ec99ce1cbffff1d5674a54d0ad.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=30544&mlfb=3VA1110-6EF46-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1110-6EF46-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1110-6EF46-0AA0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is 3VA1110-6EF46-0AA0's interrupting capacity at 240 V?","answer":"It is rated 220 kA at 240 V AC, which covers high-fault locations like transformer secondaries or large switchboards."},{"question":"What compliance documentation does this brand provide for 3VA1110-6EF46-0AA0?","answer":"The SENTRON series typically carries IEC 60947-2 certification and CE marking. Specific RoHS/REACH declarations and UL listing details should be confirmed from the manufacturer's documentation for this exact variant."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1110-6EF46-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1110-6EF46-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}