{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1110-6GD42-0AA0-ZD00","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1110-6GD42-0AA0-ZD00","canonicalUrl":"https://aoctrl.com/siemens/3VA1110-6GD42-0AA0-ZD00","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1110-6GD42-0AA0-ZD00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1110-6GD42-0AA0-ZD00, 3VA1 IEC frame 160 circuit breaker, 4-pole, breaking capacity class H Icu=70kA @ 415V, line protection TM210, In=100A, Ir=100A fixed, Ii=10 x In.","salesMarkdown":"Siemens 3VA1110-6GD42-0AA0-ZD00 is a 3VA1 IEC frame 160 circuit breaker with a breaking capacity class H rating of Icu=70kA @ 415V. Overload protection is set at In=100A with fixed Ir=100A; short-circuit protection is fixed at Ii=10 x In. The N-conductor protection is set at 100%. For a 415V distribution panel, that gives substantial headroom against high-fault utility feeds or large transformer secondaries. The TM210 trip unit means a thermal-magnetic with a 10x In magnetic trip threshold, suited for motor starting inrush or transformer energization where nuisance tripping from harmonics is a concern. ## Deployment Context The 4-pole configuration covers three-phase plus neutral, with 100% N-conductor protection — important where the neutral carries significant harmonic current (e.g., VFD-fed loads or LED lighting banks). The nut keeper kit is a panel-builder touch: it prevents the busbar connection hardware from vibrating loose in high-vibration environments like conveyors or compressors.","metaTitle":"Siemens 3VA1110-6GD42-0AA0-ZD00 IEC Frame 160 Breaker, 70kA","metaDescription":"Siemens 3VA1110-6GD42-0AA0-ZD00 circuit breaker, 3VA1 IEC frame 160, Icu=70kA @ 415V, 4-pole, In=100A, TM210 overload. Lifecycle: current. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1667540&mlfb=3VA1110-6GD42-0AA0-ZD00","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1110-6GD42-0AA0-ZD00/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of this breaker?","answer":"Icu=70kA @ 415V, breaking capacity class H per the IEC frame 160 designation."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1110-6GD42-0AA0-ZD00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1110-6GD42-0AA0-ZD00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}