{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1110-6GE46-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1110-6GE46-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1110-6GE46-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1110-6GE46-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1110-6GE46-0AA0, 4-pole molded case circuit breaker, 100 A continuous, TM220 thermal-magnetic release, 220 kA interrupting at 240 V.","salesMarkdown":"The interrupting ratings step down with voltage: 220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and 17 kA at 500 V or 690 V — so the 240 V figure is the headline for high-fault panels, but at 480/500 V systems the 17 kA SCCR governs the coordination study. The 70 mm depth and 101.6 mm width mean it fits standard SENTRON panel footprints without gland-plate surprises. Continuous current holds at 100 A up to 50 °C ambient, then derates to 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. The 100 % N-conductor protection design means the neutral pole is rated for full phase current — no derating needed on the neutral path. Optional motor drive for remote switching is available as a field-addable accessory.","metaTitle":"Siemens 3VA1110-6GE46-0AA0 SENTRON MCCB, 100 A, 4-Pole, 220","metaDescription":"Siemens 3VA1110-6GE46-0AA0 SENTRON molded case circuit breaker, 100 A continuous, 4-pole, TM220 release, 220 kA at 240 V. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"101.6 mm","Height":"130 mm","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"121 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"98 A","at 60 °C":"96 A","at 65 °C":"94 A","at 70 °C":"91 A","Depth [In]":"2.76 in","Width [In]":"4 in","Height [In]":"5.12 in","Number Of Poles":"4","Product version":"Line protection","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"25 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Courant permanent assigné Iu":"100 A","Ground-Fault Monitoring Version":"Without","Tension assignée d'isolement Ui":"800 V","Design Of The Overcurrent Release":"TM220","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","design of the N-conductor protection":"100%","reference code / acc. to IEC 81346-2":"Q","Max. rated operational voltage Ue with DC":"600 V","Product Extension / Optional / Motor Drive":"Yes","Adjustable response value current / li max.":"1 000 A","Adjustable response value current / li min.":"1 000 A","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Max. rated operational current of the frame size":"160 A","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1.5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f0de3db30c105efbcdb4acd8f2089002.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=524144&mlfb=3VA1110-6GE46-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1110-6GE46-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What is the interrupting rating of 3VA1110-6GE46-0AA0 at 240 V?","answer":"220 kA at 240 V. At 415 V it is 154 kA, at 440 V it is 121 kA, and at 500 V or 690 V it drops to 17 kA — the voltage step matters for your coordination study."},{"question":"Where can I buy 3VA1110-6GE46-0AA0?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1110-6GE46-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1110-6GE46-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}