{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1110-6MH32-0JC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1110-6MH32-0JC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1110-6MH32-0JC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1110-6MH32-0JC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1 IEC frame 160, breaking capacity class H, 3-pole MCCB, In=100A, Icu=70kA @ 415V AC, with TM120M thermal-magnetic release, shunt trip STL 110-127V DC/AC, 2 auxiliary switches HQ, nut keeper kit.","salesMarkdown":"The Siemens 3VA1110-6MH32-0JC0 is a 3VA1 series moulded-case circuit breaker on an IEC frame 160, rated 100 A continuous current (In) with a breaking capacity class H of Icu=70 kA at 415 V AC, 3-pole. The TM120M thermal-magnetic release provides starter protection; the adjustable short-circuit release (Ii) is set 5–15 × In. The adjustable Ii (5–15 × In) allows coordination with downstream motor starters: set at 5× for general distribution or 15× for high-inrush loads like large motors. The shunt trip (STL) operates on 110–127 V DC or AC 50/60 Hz, enabling remote tripping from an emergency stop circuit or a safety PLC output. ## Deployment context The 3VA1 frame mounts in standard switchboard or panelboard enclosures; the nut keeper kit simplifies panel-builder installation by retaining the mounting hardware during assembly. The shunt trip and auxiliary switches are factory-installed, reducing field wiring time.","metaTitle":"3VA1110-6MH32-0JC0 Siemens 3VA1 MCCB, 100A, 70kA @ 415V","metaDescription":"Siemens 3VA1110-6MH32-0JC0 circuit breaker, IEC frame 160, 100A, Icu=70kA @ 415V AC, 3-pole, shunt trip 110-127V DC/AC, 2 aux switches. Current production lifecycle stage; availabl","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c1cea5ba9b6eb949a8537ae425adb081.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=409628&mlfb=3VA1110-6MH32-0JC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1110-6MH32-0JC0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1110-6MH32-0JC0 and how do I get a price?","answer":"This part is sourced to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability confirmation."},{"question":"What is the breaking capacity of this MCCB?","answer":"The ultimate breaking capacity Icu is 70 kA at 415 V AC, 3-pole, per the IEC frame 160 class H rating."},{"question":"What accessories are included with 3VA1110-6MH32-0JC0?","answer":"It includes a shunt trip (STL) rated 110–127 V DC/AC 50/60 Hz, two HQ auxiliary switches, and a nut keeper kit."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1110-6MH32-0JC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1110-6MH32-0JC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}