{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1110-6MH36-0BA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1110-6MH36-0BA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1110-6MH36-0BA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1110-6MH36-0BA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1110-6MH36-0BA0, molded case circuit breaker, 3-pole, 100A rated at 40°C, TM120M overcurrent release, 220 kA breaking capacity at 240 V, undervoltage release included.","salesMarkdown":"## Siemens SENTRON 3VA1110-6MH36-0BA0 — 100 A MCCB with Undervoltage Release Breaking capacity is the headline spec here: 220 kA at 240 V, 154 kA at 415 V, and 121 kA at 440 V. Rated 100 A from 40 °C through 50 °C, then derates: 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. Maximum power loss is 27.5 W. Panel builders should account for that heat dissipation in enclosure sizing, especially when grouping multiple breakers. The 70 mm depth is relatively shallow for a 100 A MCCB with this breaking capacity, which helps in tight enclosures. Width at 76.2 mm (3 inches) is standard for a 3-pole frame. No trip indicator or communication function on this variant — it's a straightforward thermal-magnetic breaker with undervoltage release.","metaTitle":"Siemens 3VA1110-6MH36-0BA0 SENTRON MCCB, 100A, 220kA at 240V","metaDescription":"Siemens SENTRON 3VA1110-6MH36-0BA0 molded case circuit breaker, 3-pole, 100A rated at 40°C, TM120M release, 220kA at 240V. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"121 kA","at 500 V":"7.5 kA","at 690 V":"7.5 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"98 A","at 60 °C":"96 A","at 65 °C":"94 A","at 70 °C":"91 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Starter protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"27.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA11106MH360AA0","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM120M","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB11","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"I","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=120968&mlfb=3VA1110-6MH36-0BA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1110-6MH36-0BA0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA1110-6MH36-0BA0 at 415 V?","answer":"154 kA at 415 V, which provides ample fault-current interruption for most industrial 400 V distribution systems."},{"question":"What is the closest functional second-source to 3VA1110-6MH36-0BA0?","answer":"The evidence lists 5SQ2370-2YA05, 5SQ2370-2YA04, and 5SQ2370-2YA01 as peer MPNs, but no direct functional cross-reference is documented. Verify fit by comparing ratings and dimensions against your specific application."},{"question":"Where can I buy 3VA1110-6MH36-0BA0 and how is it quoted?","answer":"This part is sourced through independent distribution and quoted to order against an RFQ. Submit a request for current availability and pricing."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1110-6MH36-0BA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1110-6MH36-0BA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}