{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1110-6MH36-0BC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1110-6MH36-0BC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1110-6MH36-0BC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1110-6MH36-0BC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1110-6MH36-0BC0, molded case circuit breaker, 3-pole, 100 A rated current, 220 kA breaking capacity at 240 VAC, starter protection design with undervoltage release.","salesMarkdown":"## MCCB for motor starter protection — 100 A continuous, 220 kA interrupting at 240 V Rated 100 A continuous at ambient temperatures up to 50 °C without derating; above that it steps down to 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C — so if the panel runs hot, the usable current drops, and that derated figure is what governs the motor full-load amp selection. Breaking capacity varies sharply with system voltage: 220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and 7.5 kA at both 500 V and 690 V. ## Built-in undervoltage release and auxiliary switch complement It also carries two factory-fitted auxiliary switches (HQ design) for remote status indication — one normally-open and one normally-closed contact per switch, giving four signal paths total to the PLC or panel indicator. The basic switch core is order code 3VA11106MH360AA0 — useful to know if you ever need to order the bare switch assembly separately for a repair rather than replacing the whole breaker. Dimensions are 130 mm height, 76.2 mm width (3 inches — standard MCCB footprint for a 3-pole frame), and 70 mm depth. The width matches the common 3-inch-per-pole spacing, so it drops into existing SENTRON mounting bases without panel modification.","metaTitle":"Siemens 3VA1110-6MH36-0BC0 SENTRON MCCB, 100 A, 3-Pole, 220","metaDescription":"Siemens SENTRON 3VA1110-6MH36-0BC0 molded case circuit breaker, 100 A rated, 3-pole, 220 kA breaking capacity at 240 VAC. Starter protection design with undervoltage release. Curre","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"121 kA","at 500 V":"7.5 kA","at 690 V":"7.5 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"98 A","at 60 °C":"96 A","at 65 °C":"94 A","at 70 °C":"91 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Starter protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"27.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA11106MH360AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM120M","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB11","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"I","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=283011&mlfb=3VA1110-6MH36-0BC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1110-6MH36-0BC0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1110-6MH36-0BC0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is the breaking capacity of 3VA1110-6MH36-0BC0 at different voltages?","answer":"Breaking capacity is 220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and 7.5 kA at both 500 V and 690 V. The high-voltage capability is significantly lower — verify available fault current at your system voltage."},{"question":"What compliance documentation does this brand provide for 3VA1110-6MH36-0BC0?","answer":"As a Siemens SENTRON MCCB, this part carries the standard IEC/UL certifications for the 3VA series. Specific documentation (RoHS, REACH, UL, IEC) is available from the manufacturer upon request — the evidence does not list individual cert marks on this variant."},{"question":"Will 3VA1110-6MH36-0BC0 drop into a panel specified around 3VA1110-5ED36-0AC0 without rewiring?","answer":"Both are 3-pole SENTRON MCCBs on the same 76.2 mm width footprint, so the physical mounting and bus-bar spacing are identical. The key difference is the trip curve and accessory configuration — verify the 5ED36-0AC0's trip unit and auxiliary contacts match your coordination study before swapping."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1110-6MH36-0BC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1110-6MH36-0BC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-14T23:40:03.092Z","lastPublished":"2026-09-14T23:40:03.092Z","indexable":true}}