{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1112-3EF32-0JC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1112-3EF32-0JC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1112-3EF32-0JC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1112-3EF32-0JC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1112-3EF32-0JC0, molded case circuit breaker, 3-pole, 125 A rated at 40 °C, 75.6 kA breaking at 240 V, line protection, shunt trip, 2 auxiliary switches.","salesMarkdown":"It carries a continuous current rating of 125 A at 40 °C, and the thermal derating curve is explicit: still 125 A at 50 °C, then 122 A at 55 °C, 120 A at 60 °C, 117 A at 65 °C, and 114 A at 70 °C. That means in a 50 °C panel you get full rated current; above that you lose about 2–3 A per 5 °C step. The interrupting ratings are where this breaker earns its place: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 11.9 kA at both 500 V and 690 V. Those are the SCCR values the breaker can safely clear without welding or rupturing — critical for a high-fault panel. This is a 3-pole unit with no undervoltage release and no ground-fault monitoring. No communication module, no trip indicator flag — you get the auxiliary contacts for position indication, but no local mechanical flag. The 3VA1112-3EF32-0JC0 measures 130 mm high, 76.2 mm wide, and 70 mm deep — a standard SENTRON 3VA footprint that mounts on a DIN rail or screws into a panel base. The 76.2 mm width (3 inches) is the 3-pole form factor; it occupies three 18 mm module spaces on the rail.","metaTitle":"Siemens 3VA1112-3EF32-0JC0 SENTRON MCCB, 125 A, 75.6 kA","metaDescription":"Siemens SENTRON 3VA1112-3EF32-0JC0 molded case circuit breaker, 125 A rated at 40 °C, 75.6 kA breaking at 240 V, 3-pole, line protection. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"75.6 kA","at 415 V":"52.5 kA","at 440 V":"32 kA","at 500 V":"11.9 kA","at 690 V":"11.9 kA","at 40 °C":"125 A","at 45 °C":"125 A","at 50 °C":"125 A","at 55 °C":"122 A","at 60 °C":"120 A","at 65 °C":"117 A","at 70 °C":"114 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"28.1 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA11123EF320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM240","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL32","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"N","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=416600&mlfb=3VA1112-3EF32-0JC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1112-3EF32-0JC0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the 3VA1112-3EF32-0JC0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of this MCCB?","answer":"It interrupts 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 11.9 kA at both 500 V and 690 V."},{"question":"What is the rated current and how does it derate with temperature?","answer":"Rated 125 A continuous at 40 °C, 45 °C, and 50 °C. It derates to 122 A at 55 °C, 120 A at 60 °C, 117 A at 65 °C, and 114 A at 70 °C (–)."},{"question":"What compliance documentation is available for this breaker?","answer":"As a Siemens SENTRON product, it is designed to meet IEC 60947-2 and UL 489 standards. Specific compliance documentation (RoHS, REACH, CE, UKCA, EAC) is available upon request at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1112-3EF32-0JC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1112-3EF32-0JC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}