{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1112-3EF36-0JM0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1112-3EF36-0JM0","canonicalUrl":"https://aoctrl.com/siemens/3VA1112-3EF36-0JM0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1112-3EF36-0JM0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1 series, IEC frame 160, circuit breaker, breaking capacity class N, 3-pole, 125A, Icu=25kA @ 415V, TM240, ATAM, clamp connection, shunt trip left 110-127V AC/DC, 2 auxiliary switches, 1 short circuit alarm switch.","salesMarkdown":"## What this breaker brings to the panel It's rated for a 125 A continuous load (In) with a thermal-magnetic TM240 trip unit providing overload protection adjustable from 88 A to 125 A (Ir) and short-circuit protection (Ii) set 5 to 10 times In. The breaking capacity lands at Icu = 25 kA at 415 V, class N — that's the standard interrupting rating for general industrial distribution panels where fault levels stay under that threshold. The 125 A continuous rating (In) with an 88–125 A thermal adjust band (Ir) means this breaker covers motor or feeder circuits where the full-load current falls in that window — you dial Ir to match the load without swapping the breaker body. The TM240 thermal-magnetic trip offers fixed magnetic pickup at 5–10× In, so it's suited for general-purpose distribution and moderate motor starting where inrush doesn't exceed about 1250 A. Clamp terminals simplify wiring on a DIN-rail or mounting-plate assembly — no lug kit needed for standard cable sizes.","metaTitle":"Siemens 3VA1112-3EF36-0JM0 Circuit Breaker, 125A, 25kA @ 415","metaDescription":"Siemens 3VA1112-3EF36-0JM0 IEC frame 160 circuit breaker, 125A, 25kA breaking capacity at 415V. Current lifecycle stage. Available to order. Request a quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1035449&mlfb=3VA1112-3EF36-0JM0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1112-3EF36-0JM0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA1112-3EF36-0JM0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution channels. Submit a request for quote (RFQ) to confirm current pricing and availability; stock levels and lead times are confirmed at quote time, not on this listing."},{"question":"What is the breaking capacity of this breaker?","answer":"The 3VA1112-3EF36-0JM0 has a rated ultimate breaking capacity (Icu) of 25 kA at 415 V AC, which places it in breaking capacity class N for the IEC 60947-2 standard."},{"question":"What accessories are included with this circuit breaker?","answer":"This variant comes with a left-mounted shunt trip rated for 110–127 V AC/DC, two auxiliary switches, and one short-circuit alarm switch, plus clamp-type terminals for wiring."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1112-3EF36-0JM0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1112-3EF36-0JM0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}