{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1112-4ED22-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1112-4ED22-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1112-4ED22-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1112-4ED22-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1112-4ED22-0AA0, molded case circuit breaker, 2-pole, 125 A, TM210 thermal-magnetic trip, line protection, breaking capacity 121 kA at 240 V AC.","salesMarkdown":"The Siemens SENTRON 3VA1112-4ED22-0AA0 is a 2-pole molded case circuit breaker (MCCB) rated 125 A continuous at 40 °C, with a TM210 thermal-magnetic trip unit. Breaking capacity reaches 121 kA at 240 V AC and 75.6 kA at 415 V AC — figures that govern fault-clearing capability in a distribution panel. The 70 mm depth and 50.8 mm width fit standard MCCB mounting footprints; IP40 on the front suits enclosed panel installation. ## Thermal derating and trip unit Rated 125 A at 40 °C, 45 °C, and 50 °C; derates to 122 A at 55 °C, 120 A at 60 °C, 117 A at 65 °C, and 114 A at 70 °C. The TM210 trip unit provides fixed thermal and magnetic settings for line protection — no adjustable long-time or short-time pickup. For DC applications, refer to the 3VA device manual for switching power limits.","metaTitle":"Siemens 3VA1112-4ED22-0AA0 SENTRON MCCB, 125 A, 2-Pole, TM21","metaDescription":"Siemens SENTRON 3VA1112-4ED22-0AA0 molded case circuit breaker, 125 A, 2-pole, TM210 trip, breaking capacity 121 kA at 240 V AC. Current production; sourced to order. Request quote","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"50.8 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"121 kA","at 415 V":"75.6 kA","at 40 °C":"125 A","at 45 °C":"125 A","at 50 °C":"125 A","at 55 °C":"122 A","at 60 °C":"120 A","at 65 °C":"117 A","at 70 °C":"114 A","Depth [In]":"2.76 in","Width [In]":"2 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"2","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"18.74 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"500 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"415 V","operating voltage / at DC / rated value":"250 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"S","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/79966cc510bf70f3f3fed478673c03a0.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=445096&mlfb=3VA1112-4ED22-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1112-4ED22-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1112-4ED22-0AA0 and get a price?","answer":"This part is sourced and quoted to order against an RFQ. Submit a request for quote; availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of 3VA1112-4ED22-0AA0?","answer":"Breaking capacity is 121 kA at 240 V AC and 75.6 kA at 415 V AC."},{"question":"What is the continuous current rating and how does temperature affect it?","answer":"Rated 125 A continuous at 40 °C, 45 °C, and 50 °C. Derates to 122 A at 55 °C, 120 A at 60 °C, 117 A at 65 °C, and 114 A at 70 °C."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1112-4ED22-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1112-4ED22-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}