{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1112-6ED32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1112-6ED32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1112-6ED32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1112-6ED32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1112-6ED32-0AA0, Molded case circuit breaker, 3-pole, 125 A at 40 °C, TM210 overcurrent release, line protection, breaking capacity 220 kA at 240 V AC.","salesMarkdown":"The TM210 thermal-magnetic release handles overloads and short-circuits; no undervoltage release or trip indicator is fitted, so this is a straight thermal-magnetic breaker for standard feeder or branch protection. Rated breaking capacity is 220 kA at 240 V, 154 kA at 415 V, 75.6 kA at 440 V, and 17 kA at both 500 V and 690 V. That is a high-interrupting-capacity (HIC) frame — it clears faults well above typical utility transformer ratings at the lower voltages, so it is suited for main or sub-main distribution where high available fault current is expected. Dimensions are 130 mm height, 76.2 mm width, 70 mm depth — a 3-pole MCCB footprint that fits standard panel mounting.","metaTitle":"Siemens 3VA1112-6ED32-0AA0 SENTRON MCCB, 125 A, 3-Pole, TM21","metaDescription":"Siemens SENTRON 3VA1112-6ED32-0AA0 molded case circuit breaker, 125 A at 40 °C, 3-pole, TM210 release, 220 kA at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"75.6 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"125 A","at 45 °C":"125 A","at 50 °C":"125 A","at 55 °C":"122 A","at 60 °C":"120 A","at 65 °C":"117 A","at 70 °C":"114 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"28.1 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=299949&mlfb=3VA1112-6ED32-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1112-6ED32-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1112-6ED32-0AA0 and get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial response."},{"question":"What are the key ratings for 3VA1112-6ED32-0AA0?","answer":"Rated 125 A at 40 °C, 3-pole, breaking capacity 220 kA at 240 V, TM210 thermal-magnetic release. Insulation voltage rated 800 V."},{"question":"What is the depth of 3VA1112-6ED32-0AA0?","answer":"Depth is 70 mm (2.76 in). Overall dimensions: 130 mm height, 76.2 mm width, 70 mm depth."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1112-6ED32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1112-6ED32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}