{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1112-6FF46-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1112-6FF46-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1112-6FF46-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1112-6FF46-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1112-6FF46-0AA0, molded case circuit breaker, 4-pole, 125 A, TM240 thermal-magnetic release, interrupting rating 220 kA at 240 V AC.","salesMarkdown":"## SENTRON 3VA1112-6FF46-0AA0 — 125 A MCCB with TM240 Release It is a line-protection device, not a motor-protection or ground-fault variant — the TM240 release is sized for feeder and distribution duty where the full-load current is close to the frame rating. Interrupting capacity varies sharply with system voltage: 220 kA at 240 V, 154 kA at 415 V, 76 kA at 440 V, and 17 kA at 500 V and 690 V. At 415 V — a common industrial distribution level — the 154 kA rating covers most utility-transformer-fed fault currents without requiring current-limiting fuses upstream. Thermal derating is mild up to 50 °C (full 125 A), then drops to 122 A at 55 °C, 120 A at 60 °C, 117 A at 65 °C, and 114 A at 70 °C. For a panel with ambient near 60 °C, the effective continuous current is 120 A — a 4% reduction that rarely forces a frame upsizing, but worth confirming if the load is already at 125 A. IP40 front protection. ## Key Ratings and Release Design Endurance is rated at 20,000 mechanical operations.","metaTitle":"Siemens 3VA1112-6FF46-0AA0 SENTRON MCCB, 125 A, 4-Pole, 220","metaDescription":"Siemens SENTRON 3VA1112-6FF46-0AA0 molded case circuit breaker, 125 A rated continuous current, 4-pole, TM240 release, interrupting capacity 220 kA at 240 V. Active production. Quo","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"101.6 mm","Height":"130 mm","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"76 kA","at 500 V":"17 kA","at 690 V":"17 kA","at 40 °C":"125 A","at 45 °C":"125 A","at 50 °C":"125 A","at 55 °C":"122 A","at 60 °C":"120 A","at 65 °C":"117 A","at 70 °C":"114 A","Depth [in]":"2.8 in","Width [in]":"4 in","Height [in]":"5.1 in","Number of poles":"4","Product version":"Line protection","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"28.1 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-40 °C","Other Measurement Function":"No","Rated continuous current Iu":"125 A","Rated insulation voltage Ui":"800 V","Ground fault monitoring version":"Without","Design of the overcurrent release":"TM240","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Design of the N-conductor protection":"50%","Reference code / acc. to DIN EN 81346-2":"Q","Max. rated operational voltage Ue with DC":"600 V","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"125 A","Adjustable response value current / li max.":"1 250 A","Adjustable response value current / li min.":"625 A","Adjustable response value current / lr min.":"88 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LI","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1.5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/34252decb3c8d7245f0b60f9e1f7e2a2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=495668&mlfb=3VA1112-6FF46-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1112-6FF46-0AA0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1112-6FF46-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1112-6FF46-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}