{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1112-6MH32-0BC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1112-6MH32-0BC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1112-6MH32-0BC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1112-6MH32-0BC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1112-6MH32-0BC0, molded case circuit breaker, 3-pole, 125 A rated, 220 kA breaking capacity at 240 V, undervoltage release, 2 auxiliary switches HQ.","salesMarkdown":"The Siemens SENTRON 3VA1112-6MH32-0BC0 is a 3-pole molded case circuit breaker (MCCB) rated 125 A at 40 °C, with a breaking capacity of 220 kA at 240 V and 154 kA at 415 V — numbers that put it in the high-interrupting class for industrial distribution panels where fault currents can hit those levels. ## Breaking capacity across voltages — what matters for selectivity At 240 V this breaker clears 220 kA; at 415 V it's 154 kA; at 440 V it drops to 75.6 kA; and at 500 V and 690 V it holds at 7.5 kA. The steep drop above 440 V means you need to check the available fault current at the point of installation — if your system runs 480 V or 600 V class, the 7.5 kA rating may force a larger frame or a current-limiting fuse upstream. Rated 125 A up to 50 °C; at 55 °C it's 122 A, at 60 °C it's 120 A, at 65 °C it's 117 A, and at 70 °C it's 114 A. The storage limit is wider because it's not under load — fine for warehousing spares. Maximum power loss is 30.6 W — that's the heat it dumps into the enclosure. If you're packing several of these in a small panel, add that to your thermal budget. Bolts into a panel or mounts on a DIN rail adapter; the depth leaves room for rear-connected bus bars.","metaTitle":"3VA1112-6MH32-0BC0 SENTRON MCCB, 125A, 220kA at 240V","metaDescription":"Siemens SENTRON 3VA1112-6MH32-0BC0 molded case circuit breaker, 125A rated, 220kA breaking at 240V, 3-pole, undervoltage release. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"220 kA","at 415 V":"154 kA","at 440 V":"75.6 kA","at 500 V":"7.5 kA","at 690 V":"7.5 kA","at 40 °C":"125 A","at 45 °C":"125 A","at 50 °C":"125 A","at 55 °C":"122 A","at 60 °C":"120 A","at 65 °C":"117 A","at 70 °C":"114 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Starter protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"30.6 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA11126MH320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM120M","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB11","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"I","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=172977&mlfb=3VA1112-6MH32-0BC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1112-6MH32-0BC0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1112-6MH32-0BC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1112-6MH32-0BC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}