{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-1AA36-0HC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-1AA36-0HC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-1AA36-0HC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-1AA36-0HC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1116-1AA36-0HC0, IEC-frame 160 switch disconnector, 3-pole, In=160 A, shunt trip (STL) 12-30 V DC / 24 V AC, 2 HQ auxiliary switches, front terminal connection.","salesMarkdown":"It is built in MCCB design but configured as a dedicated disconnector — no overload or short-circuit protection elements onboard. That means it serves as a manual load-break isolator for a 160 A circuit, not as a circuit breaker. The 160 A rating sets the maximum uninterrupted current the main contacts can carry; the switch is intended for infrequent switching of loads under rated conditions, with a mechanical latching endurance of 15,000 operations. Rated insulation voltage Ui is 800 V, and the maximum operational voltage is 690 V AC (50/60 Hz) or 500 V DC. The 3VA1116-1AA36-0HC0 occupies a 76.2 mm wide footprint on the DIN rail or panel-mount surface, with a depth of 70 mm behind the panel and a height of 130 mm. The front terminal arrangement keeps the main power conductors accessible from the front, which simplifies wiring in a dense panel layout. An optional motor drive can be added for remote motorized operation. The lifecycle stage for this order code is current production.","metaTitle":"Siemens 3VA1116-1AA36-0HC0 SENTRON Switch Disconnector, 160","metaDescription":"Siemens SENTRON 3VA1116-1AA36-0HC0 switch disconnector, 160 A rated continuous current, 3-pole, shunt trip, 2 HQ aux switches. Current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Limited To 1 S":"2 kA","Trip indicator":"No","Number of poles":"3","Product version":"in MCCB design","Voltage trigger":"Yes","lifecycle_stage":"current","Limited To 0.5 S":"2 kA","Product brand name":"SENTRON","Product designation":"Switch disconnector","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"38 W","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Rated continuous current Iu":"160 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Shunt trip (STL)","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Number of CO contacts / for auxiliary contacts":"2","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Terminal connection","Arrangement of electrical connectors / for main current circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=450967&mlfb=3VA1116-1AA36-0HC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1116-1AA36-0HC0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1116-1AA36-0HC0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What is 3VA1116-1AA36-0HC0's listed depth on this component line?","answer":"The depth is 70 mm."},{"question":"What is 3VA1116-1AA36-0HC0's listed width on this component line?","answer":"The width is 76.2 mm."},{"question":"Will 3VA1116-1AA36-0HC0 drop into a panel that was specified around 3VA1110-5EE32-0JA0 without rewiring?","answer":"Both parts share the same 70 mm depth, 76.2 mm width, and 130 mm height, so the mechanical footprint is identical. However, the 3VA1110-5EE32-0JA0 is a molded case circuit breaker with an overcurrent release, while this unit is a switch disconnector without overload or short-circuit protection. The wiring pattern for the main terminals and the shunt trip is the same front-terminal connection, but the auxiliary contact configuration differs — this unit has 2 HQ auxiliary switches (2 CO), while the peer has none. Verify the control wiring for the aux contacts before drop-in replacement."},{"question":"What compliance documentation does this brand provide for 3VA1116-1AA36-0HC0?","answer":"The product is designed to IEC standards (DIN EN 81346-2 reference code Q). Specific compliance documentation such as RoHS, REACH, UL, or IEC declarations should be confirmed at the time of order against the RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-1AA36-0HC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-1AA36-0HC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}