{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-1AA36-0KA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-1AA36-0KA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-1AA36-0KA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-1AA36-0KA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1116-1AA36-0KA0, switch disconnector in MCCB design, 3-pole, 160 A, shunt trip (STL) 220-250 V DC / 208-277 V AC, front terminal connection.","salesMarkdown":"It is a pure disconnect, not a breaker: the trip curve is absent by design (no trip indicator, no undervoltage release). What it carries is a shunt trip (STL) release rated 220-250 V DC or 208-277 V AC, letting you remote-trip the disconnect from a PLC or emergency-stop circuit. The continuous current holds flat at 160 A from 40 °C through 50 °C, then derates to 158 A at 55 °C, 155 A at 60 °C, 153 A at 65 °C, and 150 A at 70 °C — useful when the disconnect lives in a warm cabinet next to drives or transformers. The mechanical service life is 15 000 operating cycles typical, and maximum power loss is 38 W. Front protection is IP40 — fine for a panel interior, not for washdown. Front-terminal connection accepts cable lugs or busbars on the main circuit. The 3VA1116-1AA36-0KA0 shares the same 76.2 mm width, 130 mm height, and 70 mm depth as the SENTRON 3VA1 IEC frame 160 family, so it drops into the same DIN-rail or panel-mount footprint as the breaker variants. If your panel was laid out for a 3VA1112-5EE32-0AA0 (a 125 A MCCB with TM220 release), the disconnect swaps in without rewiring the bus — same three-pole front terminals, same mounting centers. The difference is functional: the disconnect has no overcurrent protection, so upstream protection must already be in place.","metaTitle":"Siemens 3VA1116-1AA36-0KA0 SENTRON Switch Disconnector, 160A","metaDescription":"Siemens 3VA1116-1AA36-0KA0 SENTRON switch disconnector, 160A continuous at 40°C, 3-pole, MCCB design, shunt trip 220-250VDC/208-277VAC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"158 A","at 60 °C":"155 A","at 65 °C":"153 A","at 70 °C":"150 A","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Switch disconnector","Undervoltage Release":"No","Design Of The Product":"in MCCB design","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"38 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Design Of The Auxiliary Switch":"Without","Design Of The Auxiliary Release":"Shunt trip (STL)","Insulation Voltage / Rated Value":"800 V","protection class IP / on the front":"IP40","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","Product Function / Communication Function":"No","Undervoltage Release With Leading Contact":"No","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","number of CO contacts / for auxiliary contacts":"0","Mechanical Service Life (Operating Cycles) / Typical":"15 000","Type Of Electrical Connection / For Main Current Circuit":"Terminal connection","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=251028&mlfb=3VA1116-1AA36-0KA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1116-1AA36-0KA0/alternatives.json"},"ai":{"faq":[{"question":"Will 3VA1116-1AA36-0KA0 drop into a panel designed for 3VA1112-5EE32-0AA0?","answer":"Yes — same 76.2 mm width, 130 mm height, 70 mm depth, same three-pole front-terminal layout. The disconnect has no overcurrent release, so upstream protection must cover that role."},{"question":"What is the shunt trip voltage rating on this disconnect?","answer":"The shunt trip (STL) release is rated 220-250 V DC and 208-277 V AC."},{"question":"Where can I buy 3VA1116-1AA36-0KA0?","answer":"Sourced and quoted to order against an RFQ through independent distribution — availability and current pricing confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-1AA36-0KA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-1AA36-0KA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}