{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-1AA46-0KC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-1AA46-0KC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-1AA46-0KC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-1AA46-0KC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1116-1AA46-0KC0, switch disconnector in MCCB design, 4-pole, 160 A, 690 V AC, 70 mm depth, 130 mm height, front terminals, IP40 front.","salesMarkdown":"## Switch disconnector in MCCB design — 160 A, 4-pole It provides visible isolation for a circuit — think of it as a load-break disconnect that you can lock out for maintenance, not a protective device (no overload or short-circuit trip elements inside). The MCCB-style body measures 130 mm high by 70 mm deep, with front-facing terminals for clamp connections. It mounts into a standard panel cutout for 160 A frame SENTRON disconnectors. The shunt trip coil and two auxiliary switches are factory-fitted, so no field assembly of accessories is needed.","metaTitle":"Siemens 3VA1116-1AA46-0KC0 SENTRON Switch Disconnector, 160","metaDescription":"Siemens SENTRON 3VA1116-1AA46-0KC0 switch disconnector in MCCB design, 160 A, 4-pole, 690 V AC, IP40 front. Current lifecycle. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Height":"130 mm","Number Of Poles":"4","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Switch disconnector","Design Of The Product":"in MCCB design","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"38 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Insulation Voltage / Rated Value":"800 V","protection class IP / on the front":"IP40","operating power / at AC-3 / at 400 V":"0 kW","operating voltage / at AC / rated value":"690 V","Product Function / Communication Function":"No","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Mechanical Service Life (Operating Cycles) / Typical":"15 000","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=425088&mlfb=3VA1116-1AA46-0KC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1116-1AA46-0KC0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1116-1AA46-0KC0 and get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing."},{"question":"What are the key ratings of 3VA1116-1AA46-0KC0?","answer":"It is a 4-pole switch disconnector rated 160 A at 690 V AC, with a rated insulation voltage of 800 V, mechanical life of 15,000 cycles, and IP40 front protection."},{"question":"Will 3VA1116-1AA46-0KC0 drop into a panel specified around 5SQ2670-2YA63?","answer":"No — the 5SQ2670-2YA63 is a 4-pole MCB (miniature circuit breaker) in a 55 mm deep DIN-rail housing with IP20. The 3VA1116-1AA46-0KC0 is a larger MCCB-style disconnect (130 mm high, 70 mm deep) with front terminals and IP40; it requires a different panel cutout and mounting arrangement."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-1AA46-0KC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-1AA46-0KC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}