{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-3ED32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-3ED32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-3ED32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-3ED32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1116-3ED32-0AA0, molded case circuit breaker, 3-pole, 160 A, TM210 thermal-magnetic release, line protection, 70 mm depth.","salesMarkdown":"The 3-pole design fits three-phase feeders. Breaking capacity is voltage-dependent: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 11.9 kA at both 500 V and 690 V. If the panel runs hot — near a transformer or in a crowded enclosure — use the 60 °C column (155 A) or 70 °C column (150 A) for your load calculation. The breaker measures 70 mm deep, 76.2 mm wide, and 130 mm high, so it occupies a standard 3-pole MCCB footprint on the DIN rail or mounting plate.","metaTitle":"Siemens 3VA1116-3ED32-0AA0 SENTRON MCCB, 160 A, 3-Pole, TM21","metaDescription":"Siemens 3VA1116-3ED32-0AA0 SENTRON molded case circuit breaker, 160 A, 3-pole, TM210 release. Breaking capacity 75.6 kA at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"75.6 kA","at 415 V":"52.5 kA","at 440 V":"32 kA","at 500 V":"11.9 kA","at 690 V":"11.9 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"158 A","at 60 °C":"155 A","at 65 °C":"153 A","at 70 °C":"150 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"38 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"N","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=358878&mlfb=3VA1116-3ED32-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1116-3ED32-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1116-3ED32-0AA0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing — no stock or price figures are published here."},{"question":"What is the breaking capacity of 3VA1116-3ED32-0AA0 at different voltages?","answer":"Breaking capacity is 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 11.9 kA at both 500 V and 690 V."},{"question":"Will 3VA1116-3ED32-0AA0 drop into a panel that was specified around 3VA1112-5EE32-0AA0 without rewiring?","answer":"Both are 3-pole SENTRON MCCBs in the same 3VA frame family, so the mounting footprint and bus-bar spacing are identical. The main difference is the overcurrent release: this unit uses a TM210 release rated 160 A, while the 3VA1112-5EE32-0AA0 uses a different release and lower amp rating. Verify the load current and release coordination before swapping — the physical fit is the same, but the protection settings are not."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-3ED32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-3ED32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}