{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-3ED32-0AA0-ZD00","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-3ED32-0AA0-ZD00","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-3ED32-0AA0-ZD00","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-3ED32-0AA0-ZD00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1 IEC frame 160, breaking capacity class N, Icu=25kA @ 415V, 3-pole, line protection TM210, FTFM, In=160A, Ir=160A fixed, Ii=10 x In, nut keeper kit for DC Power OEM in China.","salesMarkdown":"## What this breaker delivers for the line-side spec The TM210 thermal-magnetic trip unit gives fixed overload protection at Ir = 160 A and fixed short-circuit pickup at Ii = 10 × In (1600 A). No adjustment knobs; what you order is what protects the feeder. The 3-pole form factor fits a 3-module wide cutout in a typical IEC distribution board. The nut keeper kit (included per the ZD00 suffix) retains the line/load lug nuts during vibration — a detail that matters if this breaker rides a machine skid or a mobile substation. No auxiliary contacts or shunt trip are built in; those snap onto the left side as separate accessories.","metaTitle":"Siemens 3VA1116-3ED32-0AA0-ZD00 Circuit Breaker, 160A, 25kA","metaDescription":"Siemens 3VA1116-3ED32-0AA0-ZD00 IEC frame 160 breaker, 25kA Icu @ 415V, 160A TM210 overload, fixed 10xIn short-circuit. Current lifecycle stage. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1667579&mlfb=3VA1116-3ED32-0AA0-ZD00","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1116-3ED32-0AA0-ZD00/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this breaker?","answer":"IEC frame 160, 25 kA Icu at 415 VAC, 3-pole, TM210 thermal-magnetic trip with fixed Ir = 160 A and fixed Ii = 10 × In (1600 A)."},{"question":"Where can I buy 3VA1116-3ED32-0AA0-ZD00?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-3ED32-0AA0-ZD00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-3ED32-0AA0-ZD00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}