{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-3ED36-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-3ED36-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-3ED36-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-3ED36-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1116-3ED36-0AA0, molded case circuit breaker, 3-pole, 160 A, TM210 release, line protection, IP40 front.","salesMarkdown":"The Siemens SENTRON 3VA1116-3ED36-0AA0 is a 3-pole molded case circuit breaker (MCCB) rated for 160 A continuous at 40 °C ambient, with the TM210 thermal-magnetic release providing line protection. That 160 A holds flat through 50 °C — only drops to 158 A at 55 °C and 150 A at 70 °C — so in a warm enclosure you still get nearly full rating without derating the breaker itself. The interrupting capacity tells you where it can sit in the fault-current hierarchy: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 11.9 kA at both 500 V and 690 V. That means at 415 V common in European industrial panels it clears a 52.5 kA fault without upstream fuses; at 690 V the 11.9 kA still covers most motor-drive branch circuits. The breaker measures 130 mm high, 76.2 mm wide, and 70 mm deep — a standard 3-pole MCCB footprint that drops into most DIN-rail or panel-mount assemblies without re-drilling. ## Approvals and compliance documentation The insulation voltage is rated at 800 V, and the storage temperature range spans -40 °C to 80 °C, exceeding the operating range of -25 °C to 70 °C.","metaTitle":"Siemens 3VA1116-3ED36-0AA0 SENTRON MCCB, 160 A, 3-Pole, TM21","metaDescription":"Siemens 3VA1116-3ED36-0AA0 SENTRON MCCB, 160 A rated at 40 °C, 75.6 kA at 240 V. 3-pole, TM210 release, line protection. Active production. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"75.6 kA","at 415 V":"52.5 kA","at 440 V":"32 kA","at 500 V":"11.9 kA","at 690 V":"11.9 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"158 A","at 60 °C":"155 A","at 65 °C":"153 A","at 70 °C":"150 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"38 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"N","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/cf6b251c6dbf33990c74d3ac5bba96cb.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=208434&mlfb=3VA1116-3ED36-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1116-3ED36-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1116-3ED36-0AA0 and get a price?","answer":"We source this part to order against an RFQ. Submit a request and we will confirm availability and current pricing at quote time."},{"question":"What are the key ratings for 3VA1116-3ED36-0AA0?","answer":"It is a 3-pole MCCB rated 160 A at 40 °C, with interrupting capacities of 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 11.9 kA at 500 V and 690 V. It uses a TM210 thermal-magnetic release for line protection."},{"question":"What is the depth of 3VA1116-3ED36-0AA0?","answer":"The depth is 70 mm (2.76 in)."},{"question":"What is the width of 3VA1116-3ED36-0AA0?","answer":"The width is 76.2 mm (3 in)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-3ED36-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-3ED36-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}