{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-3ED36-0DF0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-3ED36-0DF0","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-3ED36-0DF0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-3ED36-0DF0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1116-3ED36-0DF0, molded case circuit breaker, 3-pole, 160 A rated continuous current Iu, TM210 thermal-magnetic overcurrent release, IP40 front protection.","salesMarkdown":"The Siemens 3VA1116-3ED36-0DF0 is a SENTRON molded case circuit breaker rated for 160 A continuous current at 40 °C, holding that full rating through 50 °C before a gentle derating curve begins — 155.2 A at 55 °C, 152 A at 60 °C, 147.2 A at 65 °C, and 140.8 A at 70 °C. Breaking capacity varies sharply with system voltage: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, 13.6 kA at 500 V, and 7.5 kA at 690 V. The 415 V figure is the one that matters for most European 400 V distribution — 52.5 kA gives comfortable headroom above typical 25–36 kA fault levels at the main switchboard. The TM210 thermal-magnetic release is a fixed-trip design — no interchangeable rating modules, so the 160 A frame is the breaker's identity. ## Panel fit and auxiliary configuration The breaker measures 76.2 mm wide, 130 mm tall, and 70 mm deep — a standard 3-pole MCCB footprint that fits SENTRON panel-mounting plates and busbar systems without adaptors. The UVR coil drops the breaker on loss of control voltage — standard for emergency-stop or undervoltage protection schemes. The auxiliary trip accessory order code is 3VA9608-0BB25 if a spare is needed.","metaTitle":"Siemens 3VA1116-3ED36-0DF0 SENTRON MCCB, 160 A, 3-Pole, TM21","metaDescription":"Siemens 3VA1116-3ED36-0DF0 SENTRON molded case circuit breaker, 160 A rated, 3-pole, TM210 release, 75.6 kA at 240 V. Current production. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"75.6 kA","at 415 V":"52.5 kA","at 440 V":"32 kA","at 500 V":"13.6 kA","at 690 V":"7.5 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"155.2 A","at 60 °C":"152 A","at 65 °C":"147.2 A","at 70 °C":"140.8 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"1 auxiliary switch + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"160 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB25","Design of the overcurrent release":"TM210","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"1 A","Adjustable response value current / li min.":"10 A","Adjustable response value current / lr min.":"1 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"N","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1.5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=111800&mlfb=3VA1116-3ED36-0DF0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1116-3ED36-0DF0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1116-3ED36-0DF0 and get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at quote time."},{"question":"What breaking capacity does 3VA1116-3ED36-0DF0 have at 415 V?","answer":"52.5 kA at 415 V. That is the relevant figure for most 400 V distribution systems and provides comfortable headroom above typical 25–36 kA fault levels."},{"question":"Does the 3VA1116-3ED36-0DF0 include an undervoltage release?","answer":"Yes, it has an integrated undervoltage release (UVR) as the auxiliary release, plus one auxiliary switch and one trip alarm switch (HQ)."},{"question":"What is the temperature derating for 3VA1116-3ED36-0DF0 above 50 °C?","answer":"The breaker holds 160 A at 40 °C, 45 °C, and 50 °C. Above that it derates to 155.2 A at 55 °C, 152 A at 60 °C, 147.2 A at 65 °C, and 140.8 A at 70 °C."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-3ED36-0DF0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-3ED36-0DF0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}