{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-3EF36-0DA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-3EF36-0DA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-3EF36-0DA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-3EF36-0DA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1116-3EF36-0DA0, 3-pole molded case circuit breaker, 160 A, TM240 thermal-magnetic release, line protection, interrupting capacity 75.6 kA at 240 V.","salesMarkdown":"## MCCB for line protection with undervoltage release Interrupting capacity is 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 11.9 kA at both 500 V and 690 V, covering most industrial fault-current scenarios. Current rating holds at 160 A from 40 °C through 50 °C, then derates to 158 A at 55 °C, 155 A at 60 °C, 153 A at 65 °C, and 150 A at 70 °C. Maximum power loss is 40.5 W. Dimensions are 130 mm height, 76.2 mm width, 70 mm depth — a standard 3-pole MCCB footprint that drops into most DIN-rail or panel-mount assemblies without re-drilling.","metaTitle":"Siemens 3VA1116-3EF36-0DA0 SENTRON MCCB, 160 A, 3-Pole, TM24","metaDescription":"Siemens SENTRON 3VA1116-3EF36-0DA0 molded case circuit breaker, 160 A, 3-pole, TM240 release, 75.6 kA at 240 V. Active production, sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"75.6 kA","at 415 V":"52.5 kA","at 440 V":"32 kA","at 500 V":"11.9 kA","at 690 V":"11.9 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"158 A","at 60 °C":"155 A","at 65 °C":"153 A","at 70 °C":"150 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"40.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA11163EF360AA0","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM240","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB25","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"N","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=308670&mlfb=3VA1116-3EF36-0DA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1116-3EF36-0DA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1116-3EF36-0DA0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What is the interrupting capacity of 3VA1116-3EF36-0DA0 at 415 V?","answer":"52.5 kA at 415 V, with higher ratings at lower voltages (75.6 kA at 240 V) and lower at higher voltages (11.9 kA at 690 V)."},{"question":"What does the TM240 release mean?","answer":"TM240 is a thermal-magnetic overcurrent release with a fixed thermal rating of 160 A and magnetic trip calibrated for the 240 A frame, providing both overload and short-circuit protection for line-feeder applications."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-3EF36-0DA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-3EF36-0DA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}