{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-4ED16-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-4ED16-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-4ED16-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-4ED16-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1116-4ED16-0AA0, 1-pole molded case circuit breaker, 160 A rated current, TM210 LI overcurrent release, 75.6 kA breaking capacity at 240 V AC.","salesMarkdown":"## SENTRON 3VA1116-4ED16-0AA0 — 160 A single-pole MCCB with TM210 release The fixed short-circuit release trips at 1600 A (10× Iu), so it clears hard faults fast without adjustment. ## Breaking capacity and voltage ratings For DC circuits the maximum operational voltage is 125 V, so it works in DC branch protection or battery distribution applications within that limit. Full 160 A rating holds up to 50 °C ambient. Above that it derates linearly: 158 A at 55 °C, 155 A at 60 °C, 153 A at 65 °C, and 150 A at 70 °C. The 25.4 mm (1 in) width per pole means this single-pole unit occupies one standard DIN slot; depth is 70 mm (2.76 in), height 130 mm (5.12 in). Front IP40 protection keeps tools and fingers out but it's not sealed against washdown.","metaTitle":"Siemens 3VA1116-4ED16-0AA0 SENTRON MCCB, 160 A, 1-Pole, TM21","metaDescription":"Siemens 3VA1116-4ED16-0AA0 SENTRON molded case circuit breaker, 160 A rated, 1-pole, TM210 LI release. Breaking capacity 75.6 kA at 240 V AC. Active production. Sourced to order ag","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"25.4 mm","title":"3VA1116-4ED16-0AA0","Height":"130 mm","at 240 V":"75.6 kA","at 415 V":"9 kA","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"158 A","at 60 °C":"155 A","at 65 °C":"153 A","at 70 °C":"150 A","Depth [In]":"2.76 in","Width [In]":"1 in","Height [In]":"5.12 in","description":"circuit breaker 3VA1 IEC frame 160 breaking capacity class S Icu=36kA @ 240V 1-pole, line protection TM210, FTFM, In=160A overload protection Ir=160A fixed short-circuit protection Ii=10 x In clamp connection","Number Of Poles":"1","Product version":"Line protection","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"12.67 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Courant permanent assigné Iu":"160 A","Ground-Fault Monitoring Version":"Without","Tension assignée d'isolement Ui":"500 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","reference code / acc. to IEC 81346-2":"Q","Max. rated operational voltage Ue with DC":"125 V","Product Extension / Optional / Motor Drive":"No","Adjustable response value current / li max.":"1 600 A","Adjustable response value current / li min.":"1 600 A","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"S","Max. rated operational current of the frame size":"160 A","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1.5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7feb1478d5d9b023c255dd68dcd8cf16.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=260364&mlfb=3VA1116-4ED16-0AA0"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA1116-4ED16-0AA0?","answer":"Submit an RFQ through this listing. We source the 3VA1116-4ED16-0AA0 to order from our independent supply network; current pricing and availability are confirmed at quote time."},{"question":"When sourcing 3VA1116-4ED16-0AA0, what's the closest functional second-source — 3VA1112-5EE32-0AA0?","answer":"The 3VA1112-5EE32-0AA0 is a different variant in the same SENTRON 3VA family, but it carries a lower current rating and a different release. The 3VA1116-4ED16-0AA0 is a 160 A single-pole with TM210 release; the 3VA1112-5EE32-0AA0 is a different amp class. They are not drop-in substitutes without reviewing the panel's load and coordination study."},{"question":"What is 3VA1116-4ED16-0AA0's listed depth (70 mm) on this component line?","answer":"The listed depth is 70 mm (2.76 inches). That's the dimension from the mounting surface to the front of the breaker body, excluding handle throw."},{"question":"What is 3VA1116-4ED16-0AA0's listed width (25.4 mm) on this component line?","answer":"The width is 25.4 mm (1 inch) — exactly one standard DIN-rail module for a single-pole MCCB."},{"question":"Will 3VA1116-4ED16-0AA0 drop into a panel that was specified around 3VA1112-5EE32-0AA0 without rewiring?","answer":"Both are 1-pole SENTRON 3VA breakers with the same physical footprint (25.4 mm wide, 70 mm deep, 130 mm high), so they share the same DIN-rail mounting and bus-bar slot. However, the 3VA1116-4ED16-0AA0 is rated 160 A versus the 3VA1112-5EE32-0AA0's lower rating, and the release characteristics differ. Mechanical fit is identical; electrical substitution requires verifying the load current and coordination settings."},{"question":"What compliance documentation does this brand provide for 3VA1116-4ED16-0AA0 (RoHS, REACH, UL, IEC)?","answer":"As a Siemens SENTRON product, this MCCB is designed to IEC 60947-2 and carries CE marking for the European market. UL/CSA listings are typical for the 3VA series but should be confirmed per specific catalog number. RoHS and REACH declarations are available from Siemens documentation for the 3VA family."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-4ED16-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-4ED16-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}