{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-4ED32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-4ED32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-4ED32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-4ED32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1116-4ED32-0AA0, molded case circuit breaker, 3 poles, 160 A rated current, 121 kA breaking capacity at 240 V AC, TM210 overcurrent release, IP40 front protection.","salesMarkdown":"The 3VA1116-4ED32-0AA0: Breaking capacity drops as voltage climbs: 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V. That 11.9 kA floor at 690 V is the real constraint if you're running a 690 V distribution bus — verify your available fault current at that voltage, not the 240 V headline. The TM210 release holds 160 A flat from 40 °C through 50 °C, then derates to 150 A at 70 °C. In a hot panel — say next to a drive or transformer — use the 70 °C column, not the 40 °C rating. Dimensions are 76.2 mm wide, 130 mm tall, 70 mm deep — three 18 mm pole spaces, so it fits a standard DIN-rail or panel-mount footprint without surprises.","metaTitle":"Siemens 3VA1116-4ED32-0AA0 SENTRON MCCB, 160A, 3-Pole, 121kA","metaDescription":"Siemens SENTRON 3VA1116-4ED32-0AA0 molded case circuit breaker, 160A rated, 3-pole, 121kA breaking capacity at 240V AC. Current production. Sourced and quoted to order. Request RFQ","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"121 kA","at 415 V":"75.6 kA","at 440 V":"52.5 kA","at 500 V":"11.9 kA","at 690 V":"11.9 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"158 A","at 60 °C":"155 A","at 65 °C":"153 A","at 70 °C":"150 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"38 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"S","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0b0e47eb9d3251f724b87afb092cb1c7.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=198667&mlfb=3VA1116-4ED32-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1116-4ED32-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1116-4ED32-0AA0 and what is the lead time?","answer":"Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of 3VA1116-4ED32-0AA0 at different voltages?","answer":"121 kA at 240 V AC, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V."},{"question":"What are the physical dimensions of this MCCB?","answer":"76.2 mm wide, 130 mm tall, 70 mm deep — three 18 mm pole spaces."},{"question":"Will 3VA1116-4ED32-0AA0 drop into a panel specified for 3VA1112-5EE32-0AA0?","answer":"Both are 3-pole SENTRON MCCBs in the same 76.2 mm width footprint, so mechanical fit is the same. The key difference is the 160 A rating on this one versus the lower-rated sibling — verify your load current and the TM release curve before swapping."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-4ED32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-4ED32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}