{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-4ED36-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-4ED36-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-4ED36-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-4ED36-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1116-4ED36-0AA0 molded case circuit breaker, IEC frame 160, breaking capacity class S, 36 kA at 415 V, 3-pole, TM210 release, 160 A, clamp connection.","salesMarkdown":"The 3VA1116-4ED36-0AA0: It carries a TM210 thermal-magnetic release — fixed thermal rating at 160 A (Ir = 160 A) and fixed short-circuit pickup at 10 × In (Ii = 1600 A). For a 415 V distribution board, that 36 kA rating gives you headroom above the typical 25 kA SCCR for most commercial-industrial panels — useful if the transformer size or upstream fault current is on the high side. ## Thermal derating — 160 A continuous is not the whole story If your panel internal ambient runs at 60 °C — common in a sealed NEMA 12 enclosure with multiple breakers — you lose 5 A of headroom. That 76.2 mm (3-inch) width per pole is standard for a 160 A frame — it occupies three 18 mm DIN positions if using adapters, but typically this breaker bolts directly to the mounting plate rather than snapping onto DIN rail. The clamp connection terminals accept copper conductors without lug kits for most panel feed sizes.","metaTitle":"Siemens 3VA1116-4ED36-0AA0 MCCB, 160A, 36kA @ 415V, 3-pole","metaDescription":"Siemens SENTRON 3VA1116-4ED36-0AA0 molded case circuit breaker, 160A, IEC breaking capacity class S, 36kA at 415V. Active production, quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","title":"3VA1116-4ED36-0AA0","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"121 kA","at 415 V":"75.6 kA","at 440 V":"52.5 kA","at 500 V":"11.9 kA","at 690 V":"11.9 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"158 A","at 60 °C":"155 A","at 65 °C":"153 A","at 70 °C":"150 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","description":"circuit breaker 3VA1 IEC frame 160 breaking capacity class S Icu=36kA @ 415V 3-pole, line protection TM210, FTFM, In=160A overload protection Ir=160A fixed short-circuit protection Ii=10 x In clamp connection","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"38 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"S","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$921.71","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1aaf0cf0cceca48450d6365597556390.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=400201&mlfb=3VA1116-4ED36-0AA0"},"ai":{"faq":[{"question":"What are the physical dimensions of the 3VA1116-4ED36-0AA0?","answer":"Depth is 70 mm, width 76.2 mm, and height 130 mm."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-4ED36-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-4ED36-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}