{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1116-4EF32-0AA0-ZD00","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1116-4EF32-0AA0-ZD00","canonicalUrl":"https://aoctrl.com/siemens/3VA1116-4EF32-0AA0-ZD00","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1116-4EF32-0AA0-ZD00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1 IEC frame 160, breaking capacity class S, 36kA Icu @ 415V, 3-pole, TM240 thermal-magnetic trip unit, In=160A, overload Ir=112–160A, short-circuit Ii=5–10xIn, nut keeper kit for DC Power OEM in China.","salesMarkdown":"The Siemens 3VA1116-4EF32-0AA0-ZD00 is a 3-pole IEC frame 160 circuit breaker with breaking capacity class S, rated for 36 kA Icu at 415 V. It uses a TM240 thermal-magnetic trip unit — the thermal element adjustable from 112 A to 160 A (Ir), and the magnetic pickup fixed at 5 to 10 times In (800–1600 A). That means it's sized for a 160 A feeder or large motor branch circuit where you need selectivity headroom downstream. Mounts on standard DIN rail or panel-mount via the 3VA1 frame's integral lugs. The nut keeper kit (included per the order-code suffix) is for DC Power OEM builds in China — keeps the terminal nuts captive during assembly, which saves time on a panel line. No special tooling needed beyond a torque screwdriver.","metaTitle":"3VA1116-4EF32-0AA0-ZD00 circuit breaker, 160A, 36kA @ 415V","metaDescription":"3VA1116-4EF32-0AA0-ZD00 IEC frame 160 breaker, 3-pole, 36kA Icu @ 415V, TM240 thermal-magnetic trip, In=160A, Ir=112–160A, Ii=5–10xIn. Current lifecycle stage. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/23b216f91ebe5c0d77a9c29010c4dc76.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1667592&mlfb=3VA1116-4EF32-0AA0-ZD00","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1116-4EF32-0AA0-ZD00/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this breaker?","answer":"IEC frame 160, 3-pole, breaking capacity class S with 36 kA Icu at 415 V. Thermal-magnetic trip TM240: In=160 A, overload Ir adjustable 112–160 A, short-circuit Ii fixed at 5–10× In (800–1600 A)."},{"question":"Where can I buy 3VA1116-4EF32-0AA0-ZD00?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1116-4EF32-0AA0-ZD00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1116-4EF32-0AA0-ZD00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}